6
11
Alarm situation is accompanied by a broken sound alarm that can be turned off by pressing the
CONFIRM button (6)
shows the current temperature of the fireplace and the level of
air damper opening.
In the emergency of exceeding the temperature the corresponding pumps start to run to
cool off
the system. The KSL protection ha a higher priority than limiting the BUF
temperature.
!
Screen of the fireplace operation
It
’
s a stable state, that is, in order to change it you need to press the CHOOSE button (7)
During appearing this screen you can change the preset temperature of the fireplace (the
parameter). After pressing the CONFIRM button (6) the preset temperature
blinks whose value can be altered with the buttons
“
+
”
(4) or
“
-
”
(5) To confirm the changes you
need to press the CONFIRM button (6) once more.
If the manual mode is set (
) (the green LED diode (7) blinks.) you can
manually control the air damper-. The
“
+
”
button (4) causes the opening of the air damper (one step
10%) and the
“
+
”
button (5) causes its closing.
<20>
FIREPLACE Temp.
FIREPLACE MODE=MAN
There are the following operation modes of the fireplace:
MAN-
OFF-
AUTO-
ON-
Full automatic burning cycle in the fireplace (firing up - operation - burning
out).
Automatic control locked - only manual control of the air damper is
available. Green status diode
blinks.
Setting the air damper to the rest position ( the
parameter).Green status diode
doesn
’
t light.
The air damper is automatically controlled to stabilize temperature of
the water jacket. Green status diode
does light.
(1)
<50> ChokeV State OFF
(1)
(1)
Automatic operation is controlled by pressing the button
Green status
diode
lights during the fireplace operation and goes out when the burnt-out state is detected.
At the end of the burning-out phase the air damper sets to the rest position (
,
which prevents a room from cooling off and protects the water attachment against freezing.
(3)
“
ON/OFF
”
.
(1)
0%, full shut-off)
Temperature of
the water jacket
of the fireplace (T3)
Current
time
Time
zone
Operation mode
of
the fireplace
Preset
temperature
Air damper
opening
FIREPLACE
Password
The changes of important parameters are possible only at unlocked password. To unlock the password you
need to input proper sequence of digits with the buttons
“
+/-
“
. With the CHOOSE button (7) to change the
digits position and CONFIRM button (6) to acknowledge all and finish the procedure of changing the
password. The unlocked password is set to
“
0000
”
. Once again entering into the password change procedure
causes a new password to be set.
!
!
PASSWORD
„
9999
”
HAS CONSIDERABLE MEANING. IT CAUSES THE REACTIVATION OF THE PREVIOUS
PASSWORD IF PRESENT WITHOUT IT BEING EXPOSED.
PASSWORD OF PRODUCER'S SERVICE IS UNIQUE AND IS NOT DEPENDENT ON THE USER'S PASSWORD-
IT SHOUDN'T BE EXPOSED TO THE USER. INSTEAD OF THAT THE SERVICE CAN SET THE USER HIS OWN
PASSWORD.
Examples of passwords:
1.The control unit is installed with the unlocked password. The user can enter his own password e.g.
“
1234
”
.
From this moment the important parameters cannot be altered without the password being unlocked (that is,
resetting the password
“
1234
”
). After changing essential parameters the user can leave the control unit
unlocked, set any new password or enter
“
9999
”
, which activates the password
“
1234
”
2. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman enter the secret password or
“
9999
”
, the user still hasn't access to the important parameters.
3. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman leaves the control unit
unlocked, the user now has access to the important parameters. He can enter his own password like in example
No. 1.
4. Producer gives the control unit with the set password. The user cannot alter the important parameters. The
servic can change the settings with its own secret password. At the end a serviceman sets the password e.g.
“
1234
”
and tells it to the user, the user has access to the important parameters but without knowing the password
the other persons cannot make the changes.
5. The user has the unlocked control unit or his own password. Serviceman decides, the user though oughtn't
have access to the important parameters. The serviceman locks the control unit with his secret password, which
removes the user's password and locks the control unit.
6. Serviceman doesn't have to know the user's password. Always he can use his own secret password and at
the end lock with the
“
9999
”
, which reactivates the user's password.
Demonstration change of the <50> ChokeV State OFF
<50> ChokeV State OFF
parameter defining the choke valve position after powering off
the control unit (Parameters level 3):
Press:
* Repeatedly the button
“
CHOOSE
”
till the
parameter setting
screen appears.
* Button
“
CONFIRM
”
->
“
0
”
blinks
* 3 times the button
“
+
”
->
“
3
”
blinks
* Button
“
CONFIRM
”
->
“
3
”
stops blinking (the
has been chosen)
* Button
“
CHOOSE
”
-> current value of the
parameter shows up
* Button
“
CONFIRM
”
-> current value, you want to change, starts blinking
* Buttons
“
+
”
and
“
-
”
-> you set the new value
* Button
“
CONFIRM
”
-> we confirm the new value
* Repeatedly the button
“
CHOOSE
”
till the
“
***
”
parameter end setting screen appears.
PARAMETERS LEVEL
Parameters Level 3