Upside

min. 600 mm  (if this space cannot be provided, ask 

support from our company for anode modification)

Manhole 

access side

Pipe

connections

side

 

Pipe

connections

side

 

Pipe

connections

side

 

min. 750 mm

(if electric 

element exists, 

500 mm)

min. 1000 mm

(if there is no 

connection

500 mm)

TSB, TDB

PRO

6.

INSTALLATION

6.1.    

Siting

The place where the unit is to be installed must be closed and free from risk of freezing.  Damage to 

products, located in places with temperatures below +5°C or above +50°C, in extremely humid 

environments and in external spaces is not covered by the warranty.  If there is a risk of temporary 

freezing (<0°C outdoor temperatures), the tank and the coil (for TSB and TSB) must be completely 

drained.

The floor on which the unit will be placed must be strong enough to carry the filled weight and must 

be leveled.  If the location is leveled and protected against flooding, the unit can be installed without 

any pedestal.  However, it is recommended to place the unit on a suitable pedestal at a height of at 

least 10 cm to protect it from environmental influences. This pedestal can be of concrete or steel 

construction.

At the place where the unit is installed, precautions must be taken against flooding.  For this purpose, 

a suitable drainage system (floor drain, sump pit and pump etc.) capable of discharging water should 

be provided on the floor.  TANPERA shall not be liable for water leak damages that may be caused by 

the product or the piping, in places where such a measure is not taken.

The TSB and TDB series water heaters supplied with electric heating elements must be provided with 

electricity at the installation site (220 V for powers up to 2 kW, 380 V for higher powers).

6.2.     Space requirements for the installation location

When locating, it is very important that there is sufficient space around the unit for connections and 

servicing.  During installation, there must be sufficient working space left to intervene in the product 

for troubleshooting or to remove/install any connection/accessory.  Otherwise, the proper servicing 

will not be provided.  

The following dimensions must be observed when locating:

7

 

We reserve the right to make changes in technical information.

Manhole access side

Sensor connections side

min. 1000 mm

min. 1000 mm

(

if electric element exists, 

1200 mm

)

(if there is no 

connection 500 mm)

For the necessity of replacing (or repairing/modifying) the product, suitable passage and exit spaces 

and transportation facilities should be provided in order to be able

 to

 remove the unit and

 to

 install the

new one in the same place.

Upside

min. 600 mm  (if this space cannot be provided, ask  

support from our company for anode

 

modification)

  

min. 750 mm

                

min. 500 mm

Содержание TDB Series

Страница 1: ...www tanpera com STORAGE WATER HEATER TSB and TDB Series DOMESTIC HOT WATER STORAGE TANK PRO Series INSTALLATION OPERATION AND MAINTENANCE MANUEL...

Страница 2: ...e of printing However because of rapid developments in this field we cannot be held liable for changes in specifications affecting the contents of this publication COPYRIGHT Copyright Tanpera A All ri...

Страница 3: ...er heater 5 2 PRO series domestic hot water storage tank 6 INSTALLATION 6 1 Siting 6 2 Space requirements for the installation location 6 3 Transport lifting storage 6 4 Installing the pipe connection...

Страница 4: ...s and regulations are strictly kept concerning human environment protection YELLOW TRIANGLE Refer to applicable SAFETY ALERT notices within the manuel All SAFETY ALERT notices are applicable to person...

Страница 5: ...ified Type key Type code TSB Single pipe coil storage water heater TDB Double pipe coil storage water heater PRO Hot water storage tank Total storage capacity liters Nominal operating pressure bar TSB...

Страница 6: ...be put into operation before all indistinctnesses have been solved To avoid injuries and damages follow the instructions and local applicable safety regulations Also take the necessary protective meas...

Страница 7: ...th water or water mixture which is not in operation is exposed to temperatures below zero the tank can be damaged The water heater coils are only suitable for hot water or water glycol mixtures in the...

Страница 8: ...the hot water circulated in the coil The domestic hot water supply values given in the catalog are valid if the heating water inlet temperature and the flow rate corresponding to the capacity specifie...

Страница 9: ...information 6 Hot water exit Heating inlet Hot water return Heating exit Heating inlet Heating exit Capacity 100 5000 liters Designated use Hot water not exceeding 90 C Operation pressure 10 bar Mount...

Страница 10: ...drainage system floor drain sump pit and pump etc capable of discharging water should be provided on the floor TANPERA shall not be liable for water leak damages that may be caused by the product or t...

Страница 11: ...nges in technical information 8 To lift the unit itself first remove the thermoplastic cap on top and expose the transport eyebolts Particularly for the tanks with steel sheet sleeve care must be take...

Страница 12: ...with original packaging in a closed place which is absolutely free of external weather conditions Rising of the unit The pallet should be removed before mounting To remove the pallet lay down the uni...

Страница 13: ...technician We reserve the right to make changes in technical information 10 Before filling the tank with water unused connection ports should be blocked with a blind plug Electrical control panel must...

Страница 14: ...k is completely filled with water check all connections and piping for leaks This control can be made by visual inspection or by monitoring the pressure drop from the manometer in the installation Com...

Страница 15: ...perform cleaning and periodic maintenance of your product During cleaning and maintenance tools and chemicals that may cause physical and chemical damage to the enamel should not be used Maintenance...

Страница 16: ...arranty period are excluded from the warranty if it is detected that the magnesium anode is fully depleted Install the anode in place and tighten it Open the cold water valve and continue to use the p...

Страница 17: ...es Clean the strainer filter at the cold water inlet Turbid water flowing from taps Anode is depleted or not functioning Water leakage from the unit Flange or anode seal defective Safety valve opening...

Страница 18: ...e anode Replace if finished Call TANPERA service if the problem is not resolved Tank dirty Safety valve opening Unable to compensate water expansion Safety valve opening pressure is low Pressure incre...

Страница 19: ...at hasn t been authorised by TANPERA c Products that commissioning is required but are not commissioned by our After Sales Services Department or by a service organization authorized by us d Defects r...

Страница 20: ...S WITH INDIRECT PIPE COIL ELECTRIC STORAGE WATER HEATERS DOMESTIC HOT WATER STORAGE TANKS PACKAGE TYPE DOMESTIC HOT WATER SYSTEMS BUFFER TANKS EXPANSION TANKS DEAERATORS DIRT SEPERATORS HYDROLIC SEPER...