General maintenance should be performed at least once a year to ensure that the product 

continues to operate effectively and to prevent deterioration of the domestic hot water quality.

In the scope of maintenance;

For cleaning, follow these steps:

• Deactivate the heating system and remove electrical power (if present) before draining the 

tank for cleaning.

• Check the temperature of the water in the tank from the thermometer.  After cooling down 

sufficiently, close the cold water inlet valve and open the farthest hot water tap.

• Open the drain valve and empty the tank completely.

• Carefully remove the thermoplastic cover of the manhole access on the tank (see illustrations 

in Chapter 5) and the insulating material underneath.

• Remove the flange on manhole access.

• Visually check for contamination and damage by illuminating the inside of the tank with a 

strong flashlight.

• Remove residues and fouling not adhered to the inner wall of the tank and heating coil, with 

pressurized water.

• Clean the lime etc. adhered to the inner wall of the tank and the surface of the heating coil by 

using with non-hard tools such as plastic brushes etc.

• For cleaning, agents suitable for domestic use such as detergent, may be used.  In this case, 

8.

MAINTENANCE

If you wish, TANPERA service can perform cleaning and periodic maintenance of your product.

During cleaning and maintenance, tools and chemicals that may cause physical and chemical 

damage to the enamel should not be used.

 Maintenance and cleaning of the product must only be carried out by authorized, trained and 

qualified personnel.

CAUTION:

Cleaning agents may cause injury to exposed skin, eyes, and mucous membranes.  

Use of protective eyewear and gloves is strictly recommended.

We reserve the right to make changes in technical information. 

12

before use, 

disconnect

 all domestic water connections to prevent detergent from escaping 

into the installation; after use, make the system connections after thoroughly rinsing the 

inside of the tank with pressurized water.

Before starting maintenance and cleaning operations, the product must be switched off and the 

water inside must be cooled 

down

 below 40°C.

• The protective anode should be checked.

• Scaling, sedimentation and other deposits that may accumulate on the heating coil (for 

T

S

B

and TDB) and 

at

 the tank should be removed.

• The safety valve must be checked.  This can be done by raising the water pressure in the tank 

up to the safety valve opening pressure by a testing pump.

• Devices and accessories such as valves, check valves, expansion tanks, thermometers etc. on 

the unit and 

at

 the connected installation, should be checked to be in good working 

condition.

 

Defective ones must be repaired or replaced.  The filters of the strainers must be 

cleaned.

Содержание TDB Series

Страница 1: ...www tanpera com STORAGE WATER HEATER TSB and TDB Series DOMESTIC HOT WATER STORAGE TANK PRO Series INSTALLATION OPERATION AND MAINTENANCE MANUEL...

Страница 2: ...e of printing However because of rapid developments in this field we cannot be held liable for changes in specifications affecting the contents of this publication COPYRIGHT Copyright Tanpera A All ri...

Страница 3: ...er heater 5 2 PRO series domestic hot water storage tank 6 INSTALLATION 6 1 Siting 6 2 Space requirements for the installation location 6 3 Transport lifting storage 6 4 Installing the pipe connection...

Страница 4: ...s and regulations are strictly kept concerning human environment protection YELLOW TRIANGLE Refer to applicable SAFETY ALERT notices within the manuel All SAFETY ALERT notices are applicable to person...

Страница 5: ...ified Type key Type code TSB Single pipe coil storage water heater TDB Double pipe coil storage water heater PRO Hot water storage tank Total storage capacity liters Nominal operating pressure bar TSB...

Страница 6: ...be put into operation before all indistinctnesses have been solved To avoid injuries and damages follow the instructions and local applicable safety regulations Also take the necessary protective meas...

Страница 7: ...th water or water mixture which is not in operation is exposed to temperatures below zero the tank can be damaged The water heater coils are only suitable for hot water or water glycol mixtures in the...

Страница 8: ...the hot water circulated in the coil The domestic hot water supply values given in the catalog are valid if the heating water inlet temperature and the flow rate corresponding to the capacity specifie...

Страница 9: ...information 6 Hot water exit Heating inlet Hot water return Heating exit Heating inlet Heating exit Capacity 100 5000 liters Designated use Hot water not exceeding 90 C Operation pressure 10 bar Mount...

Страница 10: ...drainage system floor drain sump pit and pump etc capable of discharging water should be provided on the floor TANPERA shall not be liable for water leak damages that may be caused by the product or t...

Страница 11: ...nges in technical information 8 To lift the unit itself first remove the thermoplastic cap on top and expose the transport eyebolts Particularly for the tanks with steel sheet sleeve care must be take...

Страница 12: ...with original packaging in a closed place which is absolutely free of external weather conditions Rising of the unit The pallet should be removed before mounting To remove the pallet lay down the uni...

Страница 13: ...technician We reserve the right to make changes in technical information 10 Before filling the tank with water unused connection ports should be blocked with a blind plug Electrical control panel must...

Страница 14: ...k is completely filled with water check all connections and piping for leaks This control can be made by visual inspection or by monitoring the pressure drop from the manometer in the installation Com...

Страница 15: ...perform cleaning and periodic maintenance of your product During cleaning and maintenance tools and chemicals that may cause physical and chemical damage to the enamel should not be used Maintenance...

Страница 16: ...arranty period are excluded from the warranty if it is detected that the magnesium anode is fully depleted Install the anode in place and tighten it Open the cold water valve and continue to use the p...

Страница 17: ...es Clean the strainer filter at the cold water inlet Turbid water flowing from taps Anode is depleted or not functioning Water leakage from the unit Flange or anode seal defective Safety valve opening...

Страница 18: ...e anode Replace if finished Call TANPERA service if the problem is not resolved Tank dirty Safety valve opening Unable to compensate water expansion Safety valve opening pressure is low Pressure incre...

Страница 19: ...at hasn t been authorised by TANPERA c Products that commissioning is required but are not commissioned by our After Sales Services Department or by a service organization authorized by us d Defects r...

Страница 20: ...S WITH INDIRECT PIPE COIL ELECTRIC STORAGE WATER HEATERS DOMESTIC HOT WATER STORAGE TANKS PACKAGE TYPE DOMESTIC HOT WATER SYSTEMS BUFFER TANKS EXPANSION TANKS DEAERATORS DIRT SEPERATORS HYDROLIC SEPER...

Отзывы: