Heat Relay (“Hr”)
This parameter determines which of the two internal relays
will be engaged for heating. This setting only applies to
HEAT mode and has no effect in COOL and AUTO modes.
Programming:
1.
Press and release the SET button until the “Hr”
parameter is displayed.
2.
Press the UP or DOWN button once to display the current
parameter value. With the current value displayed, use
the UP/DOWN buttons to toggle this parameter between
the Relay 1 and Relay 2.
3.
Hold the SET button to exit programming mode OR press
and release the SET button again to advance to the next
programming parameter
This parameter is only accessible while the Thermostat Configuration
menu (“CC”) is set to “On”.
- 22 -
Heat-Modes Disable (“Hd”)
This parameter can be used to prevent the thermostat from
being set to any of the heating modes. When this parameter
is set to “1” only COOL and OFF modes are allowed.
Programming:
1.
Press and release the SET button until the “Hd”
parameter is displayed.
2.
Press the UP or DOWN button once to display the current
parameter value. With the current value displayed, use
the UP/DOWN buttons to toggle this parameter between
the 0 (allow heat mode) and 1 (disable heat mode).
3.
Hold the SET button to exit programming mode OR press
and release the SET button again to advance to the next
programming parameter
This parameter is only accessible while the Thermostat Configuration
menu (“CC”) is set to “On”.