Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
10
Installing a Rack Mount Library
c
Use the M5 nuts (PN YS41998) and M5 washers (PN YS40403)
provided in the rack mount kit to fasten the left shelf and shelf
extender together (see
).
3
Assemble the right shelf in the same manner, referring to the
Right Shelf
column of
.
Table 3 Shelf Assembly
Matrix
Figure 6 Identifying the
Shelf Extender Slots
Note:
Tighten the nuts to finger-tightness only; you need to be able
to retract and extend the assembled shelves slightly.
Rack Depth
(between flanges)
Left Shelf
Right Shelf
Shelf
Extender
Slots
Shelf
Extender
Slots
24.50 in. - 26.75 in.
(620 mm - 680 mm)
#2
A & B
#1
A & B
26.75 in. - 29.125 in.
(680 mm - 740 mm)
#1
B & C
#2
A & B
29.125 in. - 31.50 in.
(740 mm - 800 mm)
#2
B & C
#1
B & C
31.50 in. - 33.875 in
(800 mm - 860 mm)
#1
C & D
#2
B & C
33.875 in. - 36.25 in.
(860 mm - 920 mm)
#2
C & D
#1
C & D
A
B
C
D