Tandberg Data M-Series Installation Guide
Document T6423046-02 A01
February 2004
Installing a Rack Mount Library
11
Figure 7 Attaching the
Shelves to the Extenders
Installing the Rack Mount Shelves
0
To install the rack mount shelves:
1
From the six sizes of inserts provided in the rack mount kit, select the
insert type that best fits the holes in the rack rails. The insert part
numbers are:
• 213468 (for rails with 9 mm square holes)
• 213469 (for rails with 7 mm diameter unthreaded holes)
• 213471 (for rails with M6 threaded holes)
• 213472 (for rails with M5 or 12-24 UNC threaded holes)
• 213473 (for rails with 10-32 UNF threaded holes)
• 213474 (for rails with 1/4 inch diameter unthreaded holes)
The heads of the inserts (not the threads) should fit into the holes in the
rack rails smoothly and with very little play.
2
Once you have selected the inserts for your rack, set the others aside. You
will not need them for this installation.
3
Screw the inserts into the two outer holes on each end of the assembled
shelves (see
Note:
Some of the inserts have either no head or a head that has a
smaller diameter than the thread; these need to be left
protruding by about 1/8 in. (3 mm). The inserts with heads
should be tightened fully.
Extender
Shelf