                                                                                                       TX7301 Intelligent Sounder Strobe 

 

 

        Installation & Operation Manual  

                                                                                                                                 

4050100338

-Rev1.1-0916                                                                     

 

 

    TANDA UK  

                                                                                                                                           

Specifications are subject to change without prior notice 

10 

     

3.6 Tones Selection      

 
The Tones can be change according to the project requirement  

Table 1  

 

1.

 

Attach  the  programming  cable  to  1  and  6  Terminals  of  sounder  strobe.  Press 

“Power”

  to 

switch-on the unit.  

2.

 

Switch-on  the  programmer,  then  press  button 

“4” 

to  enter  to 

Setting

  mode  (Figure  15).  The 

programmer will display the actual configuration after few seconds. 
Input the desire Tone (Table 1) then press 

“Write”

 to change the setting (Figure 16).  

Note:

 

If display 

“Success”, 

means the entered tone is confirmed  (Figure 17). If display 

“Fail”,

 

means failure to program the tone. (Figure17) Tone 14, Tone 16 and Tone 17 are recognized 
by LPCB. 

3.

 

Press 

“Exit” 

key to go back Main Menu. Press 

“Power”

 to switch off the programmer. 

 
 
 
 
 
 
 
  

Parameter 

Tone 

Code 

dB(A) Output 

( high) 

dB(A) Output 

(low) 

Description  

01 

98.9 

95.7 

970Hz 

02 

100.9 

96.6 

800Hz / 970Hz @ 2Hz 

03 

102.9 

99.3 

800Hz -970Hz @1Hz 

04 

99.7 

97.4 

970Hz 1s off / 1s on 

05 

101.3 

98.7 

970Hz, 0.5s / 630Hz, 0.5s 

06 

102.7 

98.8 

500Hz - 1200Hz×3, 3.5s on / 0.5s off 

07 

106.6 

101.4 

2850Hz, 0.5s on / 0.5s off×3 / 1.5s off 

08 

106.1 

102.3 

2850Hz 0.4s on, 0.3s off 

09 

99.7 

96.6 

550Hz, 0.7s / 1000Hz, 0.33s 

10 

10 

105.7 

100.8 

1500Hz -2700Hz @ 3Hz 

11 

11 

102.3 

97.0 

2400Hz 

12 

12 

102.4 

97.0 

500Hz -1200Hz @ 0.33Hz 

13 

13 

104.4 

100.6 

2400Hz -2900Hz @ 9Hz 

14 

14 

105.7 

102.0 

2400Hz -2900Hz @ 3Hz [Default] 

15 

15 

102.0 

99.2 

800Hz-970Hz @ 3Hz 

16 

16 

102.1 

98.8 

500Hz-1200Hz, 3.75s / 0.25s off 

17 

17 

101.3 

98.7 

800Hz 1s off / 1s on [Pre-alarm] 

Содержание TX7301

Страница 1: ...TX7301 Intelligent Sounder Strobe Installation and Operation Manual TANDA UK Technology Copyright 2015 All right reserved...

Страница 2: ...nstalling the Sounder Strobe to ensure proper and safe operation of the system European Union directive 2012 19 EU WEEE directive Products marked with this symbol cannot be disposed of as unsorted mun...

Страница 3: ...ation 4 2 Installation 5 2 1 Installation Preparation 5 2 2 Installation and Wiring 5 3 Sounder Strobe Configuration 6 3 1 Preparation 6 3 2 Addressing 7 3 3 Single and Dual Address Mode 7 3 4 Typical...

Страница 4: ...he TX7004 Analogue Intelligent Fire Alarm Control Panel produced by single manufacture T A to avoid Intelligent communication compatibility problem 1 2 Feature and Benefits EN54 3 Compliance Built in...

Страница 5: ...ure 1 2 Gang electrical back box Follow the arrow mark for the correct position Do not over tighten the screws otherwise the base will twist Use M4 standard screws 2 Connect the wire in terminal as sh...

Страница 6: ...chased separately The programmer is packed with twin 1 5V AA battery and cable ready for usage once received It is mandatory for the commissioning personnel to have programmer tool in order to adjust...

Страница 7: ...ectively in a given period of time In Single Address Mode When in action Evacuation stage the sounders will produce visible signal of 1 4 flashes per second at 1 20 Hz frequency and simultaneously aud...

Страница 8: ...with conflicted address number if not carefully arrange the loop addressing 4 Press Exit key to go back Main Menu Press Power to switch off the programmer 3 4 Typical and Saving Mode When Sounder Str...

Страница 9: ...for Strobe type or 6 for Sounder type then press Write to change the setting into the desire mode Figure 14 Note If display Success means the entered type is confirmed If display Fail means failure to...

Страница 10: ...s failure to program the tone Figure17 Tone 14 Tone 16 and Tone 17 are recognized by LPCB 3 Press Exit key to go back Main Menu Press Power to switch off the programmer Parameter Tone Code dB A Output...

Страница 11: ...vice on the control panel to prevent false alarm 3 Do not attempt to repair the circuitry of the alarm warning device it may affect the operation to respond to a fire condition and will void the manuf...

Страница 12: ...x27 5V Min 20V Max27 5V Min 20V Max27 5V Min 18V Max27 5V Min 18V 15 92 1 87 8 95 8 91 2 84 8 86 6 83 9 84 1 45 93 1 88 6 96 7 91 7 84 8 83 6 89 0 88 6 75 96 5 92 7 101 1 97 1 88 1 89 2 90 8 89 2 105...

Страница 13: ...these parts could fail at any time Therefore test your alarm warning device at least every half year according to national codes or laws Any fire alarm devices or any other components of the system m...

Отзывы: