MAINTENANCE

9

TROUBLESHOOTING

Sometimes inactive.

Analyze possible problems according to the following table. 
If normal operations cannot be restored by this means, contact either the dealer from whom you bought the unit or TAKEX.

Trouble

Possible cause

Corrective action 

Completely inactive

Either power is OFF (including broken cable) or 
power voltage is too low.

Not yet 1 min. after power turned on.

  (Is alarm LED flickering ?)  

There is an obstacle in front of the detection area. 

Check the power cable and adjust power voltage 
properly.

Reposition so that the range is less than 40ft. (12m) 

  (wide angle) or 82ft. (25m) (vertical curtain)

Allow for warm-up time.

Remove the object.

Improper detection area adjustment. 

Improper detection area adjustment .

Readjust the detection area setting.

Readjust the detection area setting.

Cover surface soiled. 

Clean cover with a soft cloth.

   (Do not use thinner, etc.)

The detection range exceeds.

  12m (wide angle) 
  25m (Vertical curtain)

Activated when no 
person has passed.

Improper power supply.

Correct power supply.

Something moving in protected area or too rapid 
temperature variations. 

Trouble alarm initiated again after warming-up 
period,though power is reset. 

A source of electrical noise (broadcasting station, 
amateur radio etc.) nearby. 

Strong sunlight reflection or direct light hitting 
the unit.

The detector reacts to passersby outside. 

Remove the cause.

Change the installation location.

Change the installation location.  

Shield sunrays with a blind.

Readjust the detection area.

Alarm LED lights,
though connected
units are inactive.

Poor contact output connection or broken wire.

Check the wiring.

Connected units are damaged.

Check connected units.

Damaged alarm contact. 

Check alarm output terminals with tester.

Alarm LED continues 
to light and alarm
continues to be initiated. 
(Trouble alarm)

Head unit fails to be replaced.

Replace to armed position.

Too low power voltage.

Adjust power voltage properly.

There is a possibility of inner broken wire/damage.

7

To clean the device, use a soft, wet cloth and then wipe off any water drops.

If the device is particularly dirty, dip the soft cloth in the water that contains a weak neutral detergent. Wipe the 

device gently with the cloth, then wipe off any detergent that remains. Do not use substances such as thinner or 
benzene. (The plastic parts may deform, discolor or change their properties.)
Perform operation checks on a regular basis.

8

OPERATION CHECK

When installation is completed, turn the power "ON" and check operation, after about 1min. warming up time, as 
follows:

1. Make sure that alarm LED finishes flickering.

2. Walk test in the protected area to check if an alarm is 

initiated. 
Check alarm LED and control panel for sensor operation.

3. After correct operation has been confirmed, use the mode 

selector inside the sensor unit to disable the alarm LED, if 
required.

Содержание PA-5312E

Страница 1: ...or damage to the unit if the unit falls as well as prevent the sensor from being tampered Mount the unit on a solid ceiling or wall surfaces where reinforcement materials are used If you mount the unit on non wood materials of plaster board or concrete securely mount it using anchors and mounting screws that match the wall materials Unstable mounting may result in injury and or property damage if ...

Страница 2: ...n electric shock fire and or malfunction Do not install the unit in places subject to oil smoke or steam high humidity and or a lot of dust Electricity that travels through these substances may result in fire electric shock and or false operation Ask qualified personnel for any electrical work necessary for installation if required Failure to follow this may result in fire and or electric shock Th...

Страница 3: ...ill come off easily Attach the base unit with the arrow pointing to the direction of ceiling Refer to 5 WIRING and connect terminals Twist cover counter clockwise while pushing cover locking lever as the figure to detach cover Snap off limit pin near the parabolic mirror which release the mirror to turn to wall mount area Set area by area selector Put the cover on the channel of cover spacer acces...

Страница 4: ...t 1160m 22000ft 6700m 5900ft 1800m 34000ft 10400m AWG 22 Dia 0 65mm AWG 18 Dia 1 0mm AWG 16 Dia 1 25mm 9300ft 2840m 55000ft 16500m 6 AREA SETTING PA 5312E Indicator Ceiling mount Ceiling mount Wall mount PA 5325E Ex In case of 10 3m ceiling mount height and 40 12m range selector should be set at E Ex In case of 13 4m wall mount height and 33 10m range selector should be set at 9 Ex In case of 10 3...

Страница 5: ...5 Coverage can be adjusted by turning area selector in accordance with area set chart on the back of sensor unit Loosen base unit locking screw and rotate sensor unit horizontally for adjustment ADJUST UNDER AIMING POSITION DISTANCE ft m WALL 6 5 8 5 10 13 2 0 2 6 3 0 4 0 4 6 8 11 25 7 6 33 10 0 40 12 0 45 13 7 55 16 8 60 18 3 66 20 0 75 22 8 82 25 0 3 5 6 9 3 4 5 7 2 4 5 6 2 3 4 5 2 3 4 5 1 2 3 4...

Страница 6: ...TACT CHENGEOVER SETTING OF SENSITIVITY SLIGHT MOTION DETECTION Switch 3 ON N O OFF N C Factory set Switch 6 ON Slight motion OFF Intruder detection Factory set Change alarm contact to N O when sensor is used for an application except security purpose such as light control When operation check shows you high sensitivity of sensor change setting of sensitivity with mode selector and re check operati...

Страница 7: ...it The detector reacts to passersby outside Remove the cause Change the installation location Change the installation location Shield sunrays with a blind Readjust the detection area Alarm LED lights though connected units are inactive Poor contact output connection or broken wire Check the wiring Connected units are damaged Check connected units Damaged alarm contact Check alarm output terminals ...

Страница 8: ...mm 2 31 59 3 26 83 5mm Ceiling mount Wall mount Mounting hole Ceiling mount horizontal angle adjustment Vertical angle adjustment Sensor locking screw Cover locking screw Silver White 0 18 4 5m m 25 45 30 9 0 2 0 φ7 49 φ192mm φ6 63 φ170mm 0 27 7mm 2 03 52mm 1 60 41mm 1 40 36mm Flush mount attachment BU 5300 Sensor unit Plate Flush mount box Mounting hole 8 Limited Warranty TAKEX products are warra...

Отзывы: