- 24 -
EASY LINK SYSTEM
The T-M32 can be connected with other T-M32’s with communication cables to work as a
multiple manifold system.
•
The Easy Link system can connect up to 4 units.
•
A communication cable (gray color) comes with each unit. The cables use 18 gage wire
and can be up to 250ft. long all together.
You can manifold from 2 units to 4 units without a multi-system controller. A 4-unit system has
full automatic modulation between 24,000 BTU/h and 960,000 BTU/h.
•
The T-M32 Easy Link system is limited to
4 units
. If you connect more than 4
units, the first 4 units will work as part of the Easy Link system, but the other
additional units will only work as individual units.
•
The T-M32 cannot be linked with other different Takagi
models in the Easy-Link system.
Cold
Hot
Gas
Do not touch the Multi-
System connectors.
To change the dipswitch
settings for the Easy Link
system, locate the left bank
of dipswitches below the 7-
seg LED.
Do not adjust
the right
bank of dipswitches.
7-Seg LED
Right bank of
dipswitches
Left bank of
dipswitches
Easy Link connectors
are on each unit’s
computer board.
CAUTION