Pro Pump Controller (ProCon-100)
Rev3.6
2023/07/17
66/70
Copyright
©
2023 by TAEHA CORP. All Rights Reserved
9
$,K,Data,#
Pressure sensor setting
ex) $,K,1,300,10,#
① $ : STX (
command start)
② K :
pressure sensor setting command
③ Data
- Using Set : 1(ON), 0(OFF)
- Setting pressure : 300 (300 kPa)
- Tolerance : 10 (10%)
④ # :
ETX (command complete)
Host controller
➔
Procon-100
(REQUST)
10
$,K,!,# - normal
$,K,?,Data,# -abnormal
Response pressure sensor setting
ex) $,K,!,# (normal) // $,K,?,0,# (BUSY)
① $ : STX (
command start)
②
K : Pressure sensor setting command
③ ! :
Normal reception complete
? : Abnormal reception
④ Data
<Abnormal reception status>
- 0 : Busy status
- 1 : Data format error
- 2 : Data input range error
⑤ # :
ETX (command complete)
Procon-100
➔
host controller
(RESPONSE)
11 $,L,#
Request pressure sensor information
ex) $,L,#
① $ : STX (
command start)
② O :
Request pressure sensor information command
③ # :
ETX (command complete)
Host controller
➔
Procon-100
(REQUST)
12
$,L,!,Data,# - normal
$,L,?,Data,# - abnormal
Response pressure sensor information
ex) $,L,!,300,1,320,10,# (normal) //
$,L,?,0,# (BUSY)
① $ : STX (
command start)
② L :
Request pressure sensor information command
③ ! :
Normal reception complete
? : Abnormal reception
④ Data
<Normal reception sattus>
- Current pressure : 300 (300 Kpa)
- Using Set : 1 (ON)
- Setting pressure : 320 (320Kpa)
- Tolerance : 10 (10%)
<Abnormal reception status>
- 0 : Busy status
- 1 : Data format error
- 2 : Data input range error
⑤ # :
ETX (command complete)
Procon-100
➔
host controller
(RESPONSE)