Assembly and installation
5.1
Installation on brickwork
CAUTION!
Danger of injury due to a falling fresh water station
If the load bearing capacity of the installation loca-
tion or the parts used for bolting it in place are not
dimensioned for the weight of the fresh water sta-
tion, this will result a danger of crush injuries and
danger of property damage due to the fresh water
station falling down.
– Ensure that the wall has a sufficient load bearing
capacity. If necessary, consult a structural engi-
neer.
– Ensure that the parts used for bolting the station
in place are dimensioned for the weight of the
fresh water station.
– Weight specifications can be found in chapter
Chapter 14 ‘Technical data’ on page
62.
Requirements of the installation location:
n
The room must be dry and frost-free.
n
The installation location must satisfy protection class IP30.
n
The installation location must be designed for the dimensions of
the fresh water station. The dimensions can be found in chapter
Chapter 14 ‘Technical data’ on page
62.
n
The fresh water station must be connected to a mains voltage of
230
VAC
±
10% with a grid frequency of 50–60
Hz.
Requirements of the water quality:
n
Minimise corrosion and limescale in accordance with country-
specific regulations and standards.
n
Carry out drinking water analyses in accordance with country-
specific regulations and standards.
n
If applicable, install suitable water filters in the drinking water
inlet line in the building infeed line.
Falling fresh water station
Requirements for the installation loca-
tion and water quality
TACOTHERM FRESH PETA 2 / PETA 2 X
Assembly and installation
V02.2020 11/2020
Item no. 215747
EA no. 1329
Operating instructions