Note
* Reset function
Press the plus and minus buttons simultaneously for 5s to restore
the factory settings. The clock is set back to Tuesday 8:00 a.m.
Special operating conditions
1. Limit for continuous operation
The maximum running time of the pump is 30 minutes, after that
it goes into a 5-minute idle state above. If the start conditions
(temperature, timer „on“) are met, it will run back again.
2. Frost protection
When the water temperature is lower than 5 degrees, the water
flow is circulated to ensure that the pipeline does not freeze. In
this case the pump will run for 5 minutes at low speed. As soon
as 10 ° C is reached on the circulation line, the frost protection
function is activated stopped.
3. Descaling protection
If the engine has not been in operation for more than 24 hours,
it will run at the lowest for 10
seconds speed operated. This ensures that the pump rotor is
not caused by limescale build-up blocked.