Data transfer with CORA-DL
The FRISTAR3 controller has a connection for CORA-DL (electrical connection on page 19). This
makes it possible to read out and preset various values. Datalogging of the values is also possible.
To work with CORA-DL, the CORA device FRISTAR3 is used on the freely programmable controller.
Input variables
Output variables
Some of these variables are hidden by default in TAPPS2.
Set temperature
[°C]
Overwrites the set temperature selected at the potentiometer
Forced DHW circ.
[On/Off] External switch on of the DHW circulation pump.
When "ON", the DHW circulation pump runs continuously.
When "OFF", automatic mode applies.
Pause time DHW circ.
[s]
After DHW circulation has ended, it can only be restarted after this
time has elapsed
Set temp. DHW circ.
[°C]
Set temperature for DHW circulation measured at the DHW circula
-
tion sensor (if not used, the cold water sensor applies)
Timeout
[Yes/No]
Digital value
Yes/No
(Yes if connection lost)
DHW temperature
[°C]
Temperature at sensor T
WW
Cold water temp.
[°C]
Temperature at sensor T
KW
Flow rate
[l/h]
Flow rate according to flow rate sensor
Prim. flow temp.
[°C]
Prim. flow temp. [°C]
DHW circ. return temp.
[°C] Temperature of the optional DHW circulation sensor T
Zirku
Eff. set temp.
[°C]
Display of the currently effective set temperature
Pump rate
[%]
0-100 % output of the PWM pump
Valve position
[%]
0 % = valve fully closed
100 % = valve fully open
Output
[kW]
Instantaneous output of the freshwater module
Energy meter rdg
[kWh]
Total energy meter reading
Water meter rdg
[m3]
Total water meter reading
Status code