13
Control with UVR67
Step-by-step instructions
The 3 outputs
A1, A2
and
A3
for the shut-off valves are switched on if the corresponding flow rate
thresholds
min1
(540 l/h),
min2
(960 l/h) and
min3
(1440 l/h) are exceeded.
Level/menu
Technician menu password
32
, expert menu PW
64
1
Expert
Ext. sensors
Adoption of the flow rate at sensor FTS9-150DL as
EXT input 1. When using an FTS5-85DL, the DL bus
index is specified as 7.
2
Expert
Sensor menu
S1
Adoption of EXT input 1 at sensor
S1
.
3
Expert
Sensor menu
S3
Adoption of EXT input 1 at sensor
S3.
4
Expert
Sensor menu
S4
Adoption of EXT input 1 at sensor
S4
.
5
Expert
System protection
Excess temp. lim
-
iter 1
Deactivation of collector excess temperature shut
-
down activated at the factory.
6
Expert
Program settings
Selection of program
496.
7
Technician
Parameters
The values
Max1, Max2
and
Max3
must be set to
"No". This eliminates their influence on the control
process.
8
Technician
Parameters
The parameter
Min1
maintains its start threshold at
54.0 °C
(
≙
540 l/h = 9 l/min). The stop threshold is
49.0 °C.
These thresholds are used to switch output
A1
.
9
Technician
Parameters
Start value
96.0 °C
(
≙
960 l/h = 16 l/min) for the value
Min2
. The stop threshold is
91.0 °C
. These thresholds
are used to switch output
A2
.
10
Technician
Parameters
Start value
144.0 °C
(
≙
1440 l/h = 24 l/min) for the
value
Min3
. The stop threshold is
139.0 °C
. These
thresholds are used to switch output
A3
.
11
Technician
Parameters
The values
Diff1, Diff2
and
Diff3
must be set to "No".
This eliminates their influence on the control process