17
Status
A status code is assigned to each status. The sum of all active status codes is output under
index 13
("Status").
Example:
A status of
3
would mean that the DHW circulation pump is running (
1
) and the DHW cir
-
culation is enabled (
2
).
DL bus
The address is set with DIP switches on the PCB of the FRISTAR3 controller, which are labelled 1, 2
and 4. These are located on the outer edge of the PCB. If the DIP switches are not in the ON position,
address 1 is assigned to the FRISTAR3 controller (factory setting). Provided no other sensors are
connected to the DL bus, no change of address is required.
The new address is derived from address 1 (= factory setting) plus the sum of all values of the DIP
switches that are set to ON.
Example
: desired address 6
= 1 (from factory settings) + 1 + 4
= DIP switches 1 and 4 must be set to ON
1
Circulation pump running
2
DHW circulation, enable
16
Sensor T.DHW circ: open circuit
32
Sensor T.DHW circ: short circuit
64
Sensor T.DHW: open circuit
128
Sensor T.DHW: short circuit
256
Sensor T.cold water: open circuit
512
Sensor T.cold water: short circuit
1024 Sensor T.primary: open circuit
2048 Sensor T.primary: short circuit
4096 Pump fault
8192 Valve fault
DIP switches