3.3. DISTRICT HEATING SYSTEMS

This application operates a two or three port valve to control the secondary water
temperature of the heat exchanger based on the outside temperature.  In
Scandinavian applications a DWT sensor can be connected to the CSC via the input
used for Room Influence.  The CSC will use the DWT sensor to control the Primary
Return Temperature.  This will ensure that the permitted limits will not be exceeded.
Space Frost Protection or room influence cannot be offered if the maximum return
sensor is used.

Where the primary medium could enable extremely high secondary water
temperatures, a dedicated safety circuit is required.

If a clock version CSC is used then the clock determines whether the compensator
operates in day or Night Set-Back (NSB) mode.  The CSC can be set to allow the
heating i.e. pump, valve etc., to run at reduced set points or turn off during the off
periods.  When in NSB mode the action of Room Influence is adjusted to work only
in a negative fashion as to reduce the flow temperature.  The flow temperature will
be lowered by 3

°

C for every 1

°

C the room temperature is above the relaxed set point

(Svn).  The compensator has 2 compensation ratios and a high limit function to
prevent excessive set points occurring.

Out of hours, if the outside temperature drops below an adjustable frost setting,
defaulted to 0

°

C, the pump is enabled and "Auto 1" is displayed on the controller.

The CSC will resume normal operation when the outside temperature increases by
2

°

C.  If a space sensor is used then this will also provide frost protection to protect

the building fabric.  The low space temperature is adjustable but is normally set to
10

°

C.  If this limit is passed then the heating will come on in boost to ensure the

fastest possible relief.  "Auto 3" will be displayed during this period.  The frost
condition will be removed when the space temperature has risen by 2

°

C.  If for any

reason, the flow temperature should fall below 5

°

C the CSC will act to remove the

possibility of frost.  The controller will start the pump and open the valve to raise the
water temperature of the system, the CSC will remain in this condition for 30
minutes.  If the water frost event occurs during a standby period, the CSC will
display "Auto 2".

If your CSC does not have a time clock then Frost Protection is not included as the
controller does not control the pump.  All frost protection must be provided by other
interlocked devices such as thermostats.

If under floor heating is used please remember to check the high limit setting as not
to allow excessive flow temperatures.

The INF setting in Fine Tune Mode must be set to 3 to enable the max. return
application and settings.

October, 03

CSC USER GUIDE

16 of 42

Содержание Satchwell Climatronic CSC5252

Страница 1: ...Satchwell Climatronic CSC5252 CSC5352 Compensator User s Guide SatchwellTM...

Страница 2: ...pecial incidental or consequential damages arising out of purchase or use of this manual or the information contained herein Do not use the product for any other purposes than those indicated in this...

Страница 3: ...3 DISTRICT HEATING SYSTEMS 16 3 3 1 Basic Wiring Diagram for District Heating Applications 18 3 4 ACTUATOR OVERRIDE FOR MAINS OUTPUT APPLICATIONS 19 3 5 ACTUATOR OVERRIDE FOR 24VAC OUTPUT APPLICATION...

Страница 4: ...352 Only 30 5 SPECIFICATION 31 5 1 CHANGING THE BATTERY 32 6 FREQUENTLY USED FUNCTIONS AND USER SETTING RECORD TABLES 32 6 1 MANUAL OVERRIDES 32 6 2 REVIEW MODE 33 6 3 HOW TO ENTER QUICK SET MODE 33 6...

Страница 5: ...l the output or flow temperature The temperature of the flow water is monitored to ensure that desired value is maintained to maximise energy savings The hot water can be supplied by a boiler or non s...

Страница 6: ...tactors 2 2 WIRING PRECAUTIONS On new installations all sensor cables must be screened with the screens connected separately to the 0V earth point provided An MICC earth plate is provided for use if M...

Страница 7: ...hange the CSC controllers programmed set point they fool the controller into believing that the space temp is above or below the ideal space temperature The CSC is primarily a water temperature contro...

Страница 8: ...ime clock See the Quick Set mode for details on setting the clock 8 Complete the configuration via the Quick Set and Fine Tune parameters Which Parameters to Change The CSC is programmed with typical...

Страница 9: ...you have a Space Sensor what will be your target Space temperature for the Day Period SVn Set Value Night Origin If you have a Space Sensor what will be your target Space temperature for the Night Pe...

Страница 10: ...and control to the NSB requirement During the event of frost out of hours the controller will display Auto 1 to indicate that the controller is working correctly Low Flow Temperature Stage Two Frost...

Страница 11: ...ntrol loop stability at frequent intervals as a part of an on going maintenance program This will ensure maximum energy savings and component life Flow High Limit Depending on your application it may...

Страница 12: ...to 1 is displayed on the controller The CSC will resume normal operation when the outside temperature increases by 2 C If a space sensor is used then this will also provide frost protection to protect...

Страница 13: ...nd or Night Set Back is used Set Up Boost Night Set Back Pump Time switch version only 230Vac Actuator ARM Mk 2 Actuator 1 Red 2 Blue 3 Black Links 7 8 and or 9 10 must be removed if Set up and or Nig...

Страница 14: ...o 1 is displayed on the controller The CSC will resume normal operation when the outside temperature increases by 2 C If a space sensor is used then this will also provide frost protection to protect...

Страница 15: ...p and or Night Set Back is used Set Up Boost Night Set Back Pump Time switch version only 230Vac Boiler Output Boiler Links 7 8 and or 9 10 must be removed if Set up and or Night Set Back is used Set...

Страница 16: ...hours if the outside temperature drops below an adjustable frost setting defaulted to 0 C the pump is enabled and Auto 1 is displayed on the controller The CSC will resume normal operation when the o...

Страница 17: ...r controlling primary water temperature in Scandinavian Public Systems Pump Time switch version only Optional Flow Temp Boiler Fig 7 A safety high thermostat may need to be used on the secondary side...

Страница 18: ...nly Links 7 8 and or 9 10 must be removed if Set up and or Night Set Back is used Set Up Boost Night Set Back Pump Clock Version only 230Vac Boiler Output Links 7 8 and or 9 10 must be removed if Set...

Страница 19: ...ride that was used Override Open Override Close Single pole relay or contact Single pole relay or contact Fig 10 Open Close Open Close When upgrading an old CSC or CSC this method reproduces the 4 5 l...

Страница 20: ...tton Selects the mode that allows setting of the Time Switch functions Tuning Button Selects the mode that allows setting of the controller parameters Enter Button Enter button for confirming the entr...

Страница 21: ...of the set parameters Day mode Removes the effect of the time schedule and makes the controller run at the day set value constantly Night mode This mode overrides the controller time schedule and dec...

Страница 22: ...y 08 00 00 00 00 00 17 00 3 Wednesday 08 00 00 00 00 00 17 00 4 Thursday 08 00 00 00 00 00 17 00 5 Friday 08 00 00 00 00 00 17 00 6 Saturday 00 00 00 00 00 00 00 00 7 Sunday 00 00 00 00 00 00 00 00 Pl...

Страница 23: ...de It shows various temperatures the status of the actuator pump and the current time and day No settings can be changed in this mode except the facilities on the manual override switch The main displ...

Страница 24: ...ymbol Description Used In Default Range Tuning Key Indicates that you are in Quick Set Mode if the arrow is lit Quick Set Mode Set Current Time and Date CSC 5352 only Quick Set Mode 00 00 to 23 59 1 t...

Страница 25: ...his ratio is used between the Changeover point Co and the flow high limit setting The value set is divided by 10 to get the actual ratio E g 30 is equivalent to a ratio of 3 1 Quick Set Mode 30 3 1 0...

Страница 26: ...er 1 to 7 with 1 representing Monday and 7 representing Sunday If you decide not to change the value at any stage press the tuning button instead 4 Press the enter button to enter the day number and t...

Страница 27: ...ne Mode at any time press the tuning key button If no keys are pressed within a period of 30 seconds then the product will return to the Review mode The user parameters that can be viewed and or adjus...

Страница 28: ...can be manually set if required Fine Tune Mode 5 1 or 5 Sensor Averaging This tells the CSC how many Room Sensors are connected to it Averaging Fine Tune Mode 1 1 to 4 Set Boiler Hysteresis Sets the...

Страница 29: ...nt the heating will come on in boost until the hysteresis 2 C has been cleared If an adjustable room sensor is used then this setting must be set to 10 C to remove frost protection Failure to do so ma...

Страница 30: ...used for the Max Return Ratio setting e g 83 0 83 Fine Tune Mode 83 10 to 127 4 5 2 To Adjust the Economy Mode CSC 5352 Only Economy mode is used to override the plant in the event of a high outside t...

Страница 31: ...2 5mm2 cross section Protection Class IP 30 Case Matt black coloured 2 piece polycarbonate case Fire resistant to UL94V 0 Mounting Wall or panel mounting Case Dimensions 144 x 144 x 136mm Panel Cut O...

Страница 32: ...CH BACK TO AUTO AFTER THE MANUAL OVERRIDE FUNCTION HAS BEEN USED WHEN THE SWITCH IS IN AN OVERRIDE CONDITION THE DISPLAY WILL FLASH AND THE OVERRIDE CONDITION WILL BE INDICATED EXCEPT IF IT IS OVERRID...

Страница 33: ...l Description Used In Valve Opening Review Mode Valve Closing Review Mode Pump Running CSC 5352 only Review Mode Controller is in Night Review Mode Display Flow Temperature Review Mode Display Room Te...

Страница 34: ...lue Sets the amount the flow temperature should be increased by during set up Quick Set Mode 10 0 to 255 C Set Flow High Limit Temperature The highest controlled flow temp used Quick Set Mode 82 0 to...

Страница 35: ...falls below the economy set value within 1 hour of the end of occupancy time the controller will remain in economy mode 1 Make sure that you are in Fine Tune mode 2 Use the and buttons to obtain the e...

Страница 36: ...n a continuous demand signal Fine Tune Mode 120 0 to 999 PB Controller Tuning C Used to tune the controller to the control system Fine Tune Mode 50 0 to 255 Select NSB action CSC 5352 only Setting thi...

Страница 37: ...CSC how many Room Sensors are connected to it Averaging Fine Tune Mode 1 1 to 4 Set Boiler Hysteresis Sets the number of C the actual flow temperature must be above the calculated flow temperature bef...

Страница 38: ...start the pump and control the valve boiler to the NSB setting until the Hysteresis 2 C outside has been cleared Fine Tune Mode 1 0 UK 1 European Low Space Temperature Setting CSC 5352 only if space s...

Страница 39: ...in Only used when a space temperature sensor is fitted The space temperature will influence the compensated flow temperature for each C error from this figure Subject to the fine tune setting INF or I...

Страница 40: ...00 2 Tuesday 08 00 00 00 00 00 17 00 3 Wednesday 08 00 00 00 00 00 17 00 4 Thursday 08 00 00 00 00 00 17 00 5 Friday 08 00 00 00 00 00 17 00 6 Saturday 00 00 00 00 00 00 00 00 7 Sunday 00 00 00 00 00...

Страница 41: ...CSC USER GUIDE October 03 41 of 42...

Страница 42: ...February 08 CSC USER GUIDE 42 of 42 S317856100_A5...

Страница 43: ......

Страница 44: ...741100 satchwell info uk tac com www tac com Copyright 2008 TAC All brand name trademarks and registered trademarks are the property of their respective owners Information contained within this docum...

Отзывы: