5.
SPECIFICATION
Type:
CSC 5252
230 Vac output, Without Clock
561-5-252
CSC 5352
230 Vac output, With Clock
561-5-352
Power Supply:
230Vac, +10%, –6%
Output Supply:
2 x 24Vac Output terminals, a total of 10VA max.
230Vac CSC
Output Relays:
2 x Single Pole ON/OFF (interlocked) 230Vac,
10A resistive, 6A inductive.
Pump Output:
Time-switch version only. 1 x 24Vac Triac, 1A
(0V switched).
Fuses:
100mA on the 230Vac input.
Power Consumption:
22VA fully loaded.
CONSTRUCTION
Ambient Temperature Limits:
Operating:
0
°
C to 50
°
C
Storage:
–10
°
C to 70
°
C
Ambient Humidity Limits:
Operating:
0 to 95% Rh non condensing
Storage:
0 to 95% Rh non condensing
Terminals:
The terminals are provided to take wire of
2.5mm
2
cross-section.
Protection Class:
IP 30
Case:
Matt black coloured 2 piece polycarbonate case.
Fire resistant to UL94V-0
Mounting:
Wall or panel mounting.
Case Dimensions:
144 x 144 x 136mm.
Panel Cut Out Size:
138 x 138mm.
Power Supply
The power supply is on the base PCB and consists of a mains transformer which
steps the controller Voltage down to 24Vac.
Memory
The controller stores all non-volatile data in an E
2
PROM such as the user set control
parameters. This means that in the event of a power failure or separation of the
controller and base unit the user set parameters will be maintained without having to
rely on battery support. The battery (3.6V Lithium AA) will power the clock whilst the
controller is powered off for a period of typically 1 year of continuous use. The
typical shelf life of the battery is 10 years.
CSC USER GUIDE
October, 03
31 of 42
Содержание Satchwell Climatronic CSC5252
Страница 1: ...Satchwell Climatronic CSC5252 CSC5352 Compensator User s Guide SatchwellTM...
Страница 41: ...CSC USER GUIDE October 03 41 of 42...
Страница 42: ...February 08 CSC USER GUIDE 42 of 42 S317856100_A5...
Страница 43: ......