25

recently, it is possible that a small amount of energy 

is  still  present  even  if  there  is  no  power  supply, 

therefore the thermostat momentarily behaves as if 

the batteries had not been removed at all.

REMEDY: 

Press the internal test button          for a second to reset 

the internal electronic circuits.

SYMPTOM: 

When the batteries are inserted, also by pressing the 

“Test” button      , the LED does not come on for 2 

seconds, briefly flashes and the thermostat doesn’t 

work.

PROBABLE REASON: 

The batteries are dead.

REMEDY: 

Correctly insert new batteries.

 

The “Installation” paragraph explains how to perform 

the operation correctly.

SYMPTOM: 

In the “Test” mode, the LED       in the thermostat 

flashes correctly, but the relay of the relative output 

in the receiver still remains off.

PROBABLE REASON: 

The  address  code  of  the  thermostat  hasn’t  been 

correctly  self-learnt  by  the  receiving  unit  or  the 

self-learning procedure hasn’t been carried out on any 

of the unit’s channels.

REMEDY: 

Carefully  following  the  “self-learning”  procedure 

described on the instructions sheet of the receiving 

unit to join the transmitter to the desired channel.

4

4

9

ENGLISH

PORTUGUÊS

DEUTSCH

ITALIANO

FRANÇAIS

ESPAÑOL

Содержание NEW WAVE DTP Series

Страница 1: ...TERMOSTATO AMBIENTE VIA RADIO WIRELESS ROOM THERMOSTAT RADIORAUMTHERMOSTAT THERMOSTAT D AMBIANCE PAR RADIO TERMOSTATO AMBIENTE V A RADIO TERM STATO AMBIENTE VIA R DIO NEW WAVE...

Страница 2: ...2 10 10 9 8 Fig 1 Abb 1 7 4...

Страница 3: ...3 Fig 2 Abb 2 10 10 7 Fig 3 Abb 3 10 Fig 4 Abb 4 14 7 13 11 12...

Страница 4: ...selecci n sonda temperatura ambiente Jumper JP1 selec o da sonda de temperatura ambiente 1 A Sonda interna abilitata default Internal probe enabled default Innensonde aktiviert Default Sonde int rieur...

Страница 5: ...frigeraci n Jumper JP3 selec o do aquecimento arrefecimento 3 C 10 minuti default 10 minutes default 10 Minuten Default 10minutes pard faut 10minutos default 10minutos pordefeito D 3minuti 3minutes 3M...

Страница 6: ...n Test presionando 2 veces el bot n test indicado con En alternativa modi car los puentes antes de poner las bater as 4 NOTE Apr s avoir modi les ponts il est conseill de forcer une mise jour en entr...

Страница 7: ...URES Power supply 2 x 1 5V alkaline AAA type batteries Duration of the batteries 6 years at TX every 10 min 2 5 years at TX every 3 min 4 years at TX every 3 min with reduced power Measurement range 5...

Страница 8: ...e references EN 60730 1 1996 R TTE normative references ETSI EN 300 220 2 v2 1 1 OVERVIEW Thisdeviceisaradio controlledelectronicthermostattocontrolthetemperature in industrial and commercial spaces a...

Страница 9: ...rom the thermostat if the same data comes from an associated timer thermostat or if the selection is decided on the receiver using the dedicated input The receiver is able to adjust the temperature in...

Страница 10: ...ems If the thermostat is installed in close proximity to the receiver 15 metres you can also choose the 3 minute mode with reduced power The batteries will last longer when you choose the longer perio...

Страница 11: ...hat it correctly comes into connect with its spindle and then pressing it down to the bottom Red LED low battery warning The red warning LED Fig 1 on the front of the product noti es when the batterie...

Страница 12: ...front slots as shown by in Fig 1 In the Test mode the thermostat continuously transmits ON and OFF commands to the receiver with a pause of approximately 2 seconds between one and the next The LED ash...

Страница 13: ...ooth and the hole in the plastic without pressing down directly on it to make sure that it doesn t break Correctly insert the batteries respecting the correct polarity Do not use dead batteries Use al...

Страница 14: ...output relay in the receiver does not come on or off instantly The status is updated every 3 or 10 minutes See the How it works section REMEDY This is a normal operation SYMPTOM When the batteries ar...

Страница 15: ...ries are dead REMEDY Correctly insert new batteries The Installation paragraph explains how to perform the operation correctly SYMPTOM In the Test mode the LED in the thermostat ashes correctly but th...

Страница 16: ...minimum section and no longer than 3 m Do not use same duct for signal wires and mains Installation and electrical wirings of this appliance must be made by quali ed technicians and in compliance wit...

Отзывы: