installation manual 

Keep  indoor  unit,  outdoor  unit,  power  supply  wiring  and  
transmission wiring at least 1 meter away from televisions  
and  radios.  This  is  to  prevent  image  interference  and  
noise  in  those  electrical  appliances.  (Noise  may  be  
generated  depending  on  the  conditions  under  which  the  
electric wave is generated, even if 1 meter is kept.)  

There is enough room for installation and maintenance. 

The ceiling is horizontal, and its structure can endure the  
weight of the indoor unit. 

The  outlet  and  the  inlet  are  not  impeded,  and  the  
influence of external air is minimum.

The air flow can reach throughout the room. 

The connecting pipe and drainpipe could be extracted out  
easily. 

There is no direct radiation from heaters. 

5.    INDOOR UNIT INSTALLATION

5.1   Installation place 

(Refer to Fig.5-1,Fig.5-2,Fig.5-3  for specification.) 

The indoor unit should be installed in a location that meets  
the following reauirements: 

5.2   Install the main body 

Please cut a square hole of 600×600mm in the ceiling 
according to the shape of the installation paper board.  

(Refer to  Fig.5-3,Fig.5-4) 

The center of the hole should be at the same position of  
that of the air conditioner body. 

Determine the lengths and outlets of the connecting pipe,  
drainpipe and cables. 

To  balance  the  ceiling  and  to  avoid  vibration,  please  
enforce the ceiling when necessary. 

Please  adjust  the  hexangular  nuts  on  the  four  installation  
hooks evenly, to ensure the balance of the body. 

If  the  drainpipe  is  awry,  leakage  will  be  caused  by  the  
malfunction of the water-level switch. 

Adjust the position to ensure the gaps between the body  
and  the  four  sides  of  ceiling  are  even.  The  body's  lower  
part  should  sink  into  the  ceiling  for  10~12  mm  

(Refer  to  

Fig.5-5) 

Use  the  transparent  hose  filled  with  water  to  check  the  
lever of the main body from the four sides or diagonal line  
direction, the lever indicator also can check the lever from  
four sides of the main body . 

(Refer to Fig.5-6) 

Locate  the  air  conditioner  firmly  by  wrenching  the  nuts  
after having adjusted the body's position well. 

Please select the position of installation hooks according to  
the hook holes on the installation board. 

Drill four holes of  

Ø 

12mm, 50~50mm deep at the selected   

positions  on  the  ceiling.  Then  embed  the  expansible  
hooks (fittings). 

Face the concave side of the installation hooks toward the  
expansible hooks. Determine the length of the installation  
hooks  from  the  height  of  ceiling,  then  cut  off  the  
unnecessary part. 

If  the  ceiling  is  extremely  high,  please  determine  the  
length of the installation hook accordingly.

Cut the installation hook open in the middle position, then  
use  apropriate  length  of  reinforcing  rod  ( 

Ø 

12)  to  weld  

together. 

The length could be calculated from  

Refer to Fig.5-5 

Length=210+L(in general, L is half of the whole length of  
the installation hook) 

New built houses and ceilings 

In the case of new built house, the hook can be embedded  
in advance (refer to the A.b mentioned above). But it should  
be  strong  enough  to  bear  the  indoor  unit  and  will  not  
become loose because of concrete shrinking. 

After installing the body, please fasten the installation paper  
board  onto  the  air  conditioner  with  bolts(M6X16)  to  
determine  in  advance  the  sizes  and  positions  of  the  hole  
opening on ceiling. 

(Refer to Fig.5-8) 

Refer to the A.c mentioned above for  installation. 

Remove the installation paper board. 

Please  first  guarantee  the  flatness  and  horizontal  of  ceiling  
when installing it. 

Refer to the A.a mentioned above for others. 

After  installing  the  body,  the  four  bolts(M6x12)must  be  
fastened  to  the  air  conditioner  onto  ensure  the  body  is  
grounded well. 

CAUTION 

CAUTION 

The existing ceiling (to be horizontal) 

Fig.5-2 

Fig.5-1 

0 8 

2       

A

 

Necessary room 

Ground 

Outlet 

Outlet 

0

 
0

 
3

 
2

 

Inlet 

0

 
0

 
0

 
1

 

>1000 

>1000 

0

 

0

 

0

 

1

 

Содержание SYSVRF CASSETTE MINI

Страница 1: ...SYSVRF CASSETTE MINI Cassette 600x600 VRF indoor unit INSTALLATION MANUAL GB...

Страница 2: ...use injury The appliance must be installed 2 3m above floor The appliance shall not be installed in the laundry Before obtaining access to terminals all supply circuits must be disconnected The applia...

Страница 3: ...liquid evaporating Other special conditions Carry out the specified installation work after taking into account strong winds typhoons or earthquakes Improper installation work may result in the equipm...

Страница 4: ...without further notices Cautions on remote controller installation Remote controller Remote controller holder Mounting screw B ST2 9x10 C H This manual Four way Cassette Four way Cassette compact INST...

Страница 5: ...main body from the four sides or diagonal line direction the lever indicator also can check the lever from four sides of the main body Refer to Fig 5 6 Locate the air conditioner firmly by wrenching...

Страница 6: ...i e h g n i l i e c H Horizontal indicator 45 5 3 Install The Panel Remove the air in grill Never put the panel face down on floor or against the wall or on uneven surfaces Never crash or strike it Sl...

Страница 7: ...rant oil and wrench it for 3 4rounds with hands before fasten the flare nuts Refer to Fig 6 1 Be sure to use two wrenches simultaneously when you connect or disconnect the pipes The stop valve of the...

Страница 8: ...or or soap water Cover the joint of the connecting pipe to the indoor unit with the sound proof insulating sheath fittings and bind it well with the tapes to prevent leakage Flaring Cut a pipe with a...

Страница 9: ...76cmHg Loosen and remove the square cover of stop valves A and B to open stop valve A and B completely then fasten them Disassemble the charge hose from the repair mouth of stop valve A and fasten the...

Страница 10: ...s should be incorporated in the fixed wiring according to the National wiring regulation Be sure to locate the power wiring and the signal wiring well to avoid cross disturbance and their contact with...

Страница 11: ...ng Regulation Ground the air conditioner properly to obtain a good anti interference effect CAUTION Model W 1500 5600 15 15 3 2 0 Circuit breaker fuse A Indoor unit power wiring mm2 Indoor outdoor con...

Страница 12: ...ation 1 means factory test mode 0 means add auto searching mode default setting 1 means DC fan is chosen 0 means AC fan is chosen 00 means DC fan static pressure is 0 reserved 01 means DC fan static p...

Страница 13: ...f COOLING with the remotecontroller andcheckthefollowingpointsperthe Owner s Manual If there is any malfunction please resolve it as per chapter Troubles And Causes The indoor unit Whether the switch...

Страница 14: ...SYSVRF CASSETTE MINI_IM EN April 2014 MDV11I 025EW...

Отзывы: