17
Switch between 12 and 24 hours time format.
• Contact information: contractor, installer, service, phone, website, e-mail, etc.
• Display settings: screen brightness and screen behavior in standby mode.
4.7.6
Service
All unit parameters and settings can be changed in the
Service
menu.
The
Service
menu is locked by default and it is necessary to enter a password (default
password is 1111).
4.7.6.1
Input
Configuration of inputs
Settings for analog, digital and universal input terminals on the main board and connection board, configuration of
functionality.
Table 1 Digital universal inputs available for selection
User modes
Activation of specific user modes.
Central Vacuum Cleaner
Activation of Central vacuum cleaner function.
Cooker hood function
Activation of Cooker Hood function.
External Stop
Air handling unit is stopped by an external command.
Extra controller Alarm
Indication about an alarm in external controller. Used for Extra Heater/Cooler/
Preheater.
Change-over feedback
Used with Change-over systems. Indicate if the temperature of heating/cooling fluid
in the system is right.
Fire Alarm
Air handling unit is stopped due to fire. Can be used with smoke alarms or similar.
Configurable Digital
Input 1
Activation of custom airflows set by user.
Configurable Digital
Input 2
Activation of custom airflows set by user.
Configurable Digital
Input 3
Activation of custom airflows set by user.
Pressure Guard
Digital input from a pressure guard component
Relative humidity and rotation speed signals from fans are already pre-addressed to specific terminals and cannot be
changed, all other inputs are free for configuration by commissioning. Inputs are free to be used for any purpose.
Universal input (UI) configured as universal analog input (UAI) can be configured for several inputs because multiple
sensors of the same type can be used. Universal analog inputs (UAI) have only selections for
RH Sensor (RH)
,
CO
₂
Sensor (CO
₂
)
,
Supply Air Fan Control (SAFC)
and
Extract Air Fan Control (EAFC)
wired configurations.
Analog input (AI) temperature sensors are not allowed to be configured more than once.
Same user modes can be configured on multiple digital inputs (for example multiple bathrooms can be connected to dif-
ferent digital inputs with
Refresh
mode configured for each.
Digital inputs can be configured to be normally open (
Normally Open (NO)
) or normally closed (
Normally Closed
(NC)
). Default setting is
Normally Open (NO)
. Not available for wireless inputs.
A time delay for user modes activated via digital input can be switched off or enabled. Time delay indicates how long
the user mode remains active after its duration of operation has expired.
PDM (pulse density modulation) input for relative humidity (RH) sensor on the main board is pre-adressed and cannot
be changed.
| 01_1.8.0