18
Table 2 Overview of input configuration
Analog inputs
Digital inputs
Universal analog inputs
Universal digital inputs
Input type
Value
Compensation
Input type
Polarity
Value
Input type
Analog type
Value
Input type
Digital type
Polarity
Value
4.7.6.2
Output
Configuration of outputs.
Settings for analog, digital and universal output terminals on the main board and connection board, configuration of
functionality.
Table 3 Digital outputs available for selection
Step controllers for
Heating/Cooling/Extra
controller
Heater/Cooler/Extra controller control signals.
Sum Alarm
Fault indicating output.
Outdoor-/Exhaust Air
Damper
Outdoor-/Exhaust air damper control signal.
Secondary Air
Secondary air damper control.
Activate Cooling
Cooling mode activation signal to an external system.
Interlock External fan
Control
Automatic indication about prohibited external fan control (i.e. if defrosting is
activated).
Circulation pump
Heating/Cooling/Extra
controller
Start/Stop signal to the circulation pump of the Heating/Cooling/Extra controller.
Fan output PWM (Pulse-width modulation) signal and triac output are already pre-addressed to specific terminals and
cannot be changed, all other outputs are free for configuration by commissioning. Outputs are free to be used for any
purpose.
Digital outputs are restricted by signal type and physical number of connections.
An output function is only allowed to be used once. Already used and configured terminal is greyed-out in the menu for
output type selection.
Analog and digital outputs have a selection for
Auto
/
Manual
modes and an adjustable value for
Manual
mode.
Manual
mode selection overwrites all system related automatic functions. Analog output adjustable manual value
range is 0–10V and digital output values
On
/
Off
.
Table 4 Overview of output configuration
Analog outputs
Digital outputs
Output type
Auto/Manual
Value
Output type
Auto/Manual
Value
4.7.6.3
Components
Configuration of connected components.
Heat Exchanger
• Choose heat exchanger type.
Available types:
Rotating
/
Plate
• Activate or deactivate passive house function if heat exchanger type
Rotating
is selected.
| 01_1.8.0