5.3
Description of Multibox MUB/F
•
smoke-removal fan
•
400°C/120 min. (F400)
•
insulated housing
•
low noise level
•
can be operated on two levels
•
tested to EN 12101-3 with LGAI, Barcelona
The smoke-removal fans of the MUB/F series are suited for conveying hot fume gases in the standard area with standard tempera-
WXUHVXSWRr&7KH08%)PXOWLER[KDVEHHQʾWWHGZLWKEDFNZDUGEHQWIUHHUXQQLQJIDQZKHHOVRIJDOYDQLVHGVWHHO7KHKRXVLQJ
FRPSULVHVDVHFWLRQHGVWHHOIUDPH$OOSDUWVKDYHEHHQJDOYDQLVHGDQGDUHUHVLVWDQWDJDLQVWWKHLQʿXHQFHRIVHDZDWHU7KHVLGH
parts comprise double-shelled panels of galvanised steel sheet with a mineral wool insulation 20 mm in thickness. They have smooth
surfaces as protection against dust and dirt deposits. The blow-out direction can be chosen quite simply between a straight and lateral
direction. The motors are aligned to use of high temperatures, F 400°C / 120 min. The motors are available as one- or two phase ver-
sions.
1
2
3
4
6
5
Fig. 6:
Multibox MUB/F
Legend
1
RSA
Sound absorber
5
WSD
Weather-protection roof
2
EVH
Elastic connection
6
MUB/F
Multibox
3
LRK
$XWRPDWLFFORVLQJʿDS
7
GFL
&RXQWHUʿDQJH
4
SDM
Service door
5.3.1
Name plate
TYPE:
MUB/F 062 630 D4 HT
400 D V
8,2 A
kW
33302 / 7367
87 / 2010-09-01
T
CAP AC
COSPH
M
WEIGHT 163 kg IP55
INS.CL. F
1
4
6
7
2
8
1
Type designation
2
Article number/ Production number / Manufacturing date
3
Voltage / Frequency / Motor output
4
Current / Speed (max./min.) / Output
6
Registration Ukraine, Russia / Weight / Protection class
7
Capacity at 1~ / Insulation class, motor
8
Temperature (TR: Temperature on ventilator)
Fig. 7:
Name plate MUB/F