Electrical connection 

DVV 16.08.2021 

6.2 

Preconditions for installation 

 

DVV fans must be installed on roofs, outside fire zone (DVV/F for exhausting from fire zone). 

 

The fans must be mounted on a flat, horizontal roof base (<10 mm/m) with height of min. 250 mm over the roof 
top (motor shaft vertical). The base shall be accordingly designed (load capacity, stiffness, insulation), if not proved 
Systemair accessories used. Extremely wind or turbulence exposed places should be avoided in order to prevent 
any water droplets ingress under extreme weather conditions. 

 

During installation the site must be protected from dust, moisture and weather influences. 

 

6.3 

Installation 

 

Ensure secure access to the fan for maintenance and service. 

 

Installation examples up to Appendix 2. Installation faults see Appendix 3. 

 

Fit the contact surface between base plate and roof base with temperature resistant sealing tape for DVV/F or 
foam sealing tape for DVV/120, DVV-T. Systemair roof bases (for smoke extract fans marked with /F) are delivered 
with appropriate sealing tape. 

 

 

WARNING 

Hazard from mechanical distortions! 

 

Before and after mounting check manually if the impeller rotates smoothly. Install the fan only, if the 
minimum air gap between rotor and nozzle matches the value from the test protocol. 

 

Avoid distortions of the casing at installation. 

 

 

The fans shall be fixed to the base with 4 screws in the corners. 

 

Ensure unobstructed and uniform intake into the fan as well as free outlet. 

 

Install connecting ducts and accessories. The suction side of the fan is provided with a connection for flange-type 
mounting of the air duct according EUROVENT, dimensions see Appendix 1 o

www.systemair.com

. 

 

Provide for contact/suction protection and safety distances according to EN ISO 13857. 
 

 

NOTE 

In some cases, it is better to mount accessories before placing the fan on the roof base. 

 

 

NOTE 

It is recommended to install a flexible connection between the fan and duct to avoid eventual tensions or 
distortions of the base plate (for F400 and F600 only: appropriate flexible connection should take eventual 
thermal extension of connecting parts. Flexible connection shall comply temperature/time class of the fan 

(400°C/2h 

respectively 

600°C/2h)

; also as certified Systemair accessory available). 

 

 

NOTE 

It is recommended to keep sufficient ventilation rate to avoid condensation in cold corners of the roof 
base under certain weather conditions or to insulate any heat bridge in case of low ventilated buildings. 

 

 

NOTE 

Data of accessories are on-line available - www.systemair.com. 

 

7

 

Electrical connection 

The wiring diagram is placed inside the cover of service switch (also in the test protocol). The quality and installation 
of cables for electrical connection must ensure uninterrupted energy supply, even in case of fire. Inside fire zone use 

Содержание DVV-XL

Страница 1: ...DVV DVVI XS XM XL XP Installation and Operating Instructions for English original version...

Страница 2: ...with Systemair also for the event of applications for protective rights Any powers of use such as copying and forwarding rights are with us An exemplary configuration has been shown on the title page...

Страница 3: ...connection 9 7 1 Residual current circuit breaker 10 7 2 Connection of thermal protection 10 8 Commissioning 10 8 1 Preconditions 10 8 2 Safety elements 11 8 3 Commissioning 11 9 Operation 11 9 1 Safe...

Страница 4: ...f injurie from rotating parts if not covered with protective grid This warning identifies situations with a danger for life from touching impeller Failure to comply with this warning leads to the risk...

Страница 5: ...sonal protective equipment Depending on object additional protective equipment may be necessary Safety components must not be by passed or put out of function Keep all the warning signs and nameplates...

Страница 6: ...uilding structure and equipment against excessive temperatures and decrease fire escalation to the surrounding areas Snow load classification SL 0 suitable for installation only on the top of heated b...

Страница 7: ...vets screws or covering caps WARNING Electrical hazard from damaged connection cable or connections Do not use the connection cable service switch or impeller for transport or hoisting WARNING Hazard...

Страница 8: ...on request recommended factory mounted as DVVI fan DVV DVVI fans can be also equipped with accessory FSL factory mounted recommended 5 1 Technical data Size DVV XS XM XL XP Max synchron RPM at 50 or...

Страница 9: ...casing at installation The fans shall be fixed to the base with 4 screws in the corners Ensure unobstructed and uniform intake into the fan as well as free outlet Install connecting ducts and accesso...

Страница 10: ...cal expert disconnect from the power supply all pole prevent switching on again test absence of voltage earthing and short circuiting protect adjacent live parts by covers and barriers and fit a suita...

Страница 11: ...ing by trained and instructed qualified personnel only Switch the ventilator on as planned WARNING Hazard from bursting parts When checking the direction of rotation wear safety goggles Check the dire...

Страница 12: ...rly important if the supply cable is long but also to reduce the motor noise Filters may only be aban doned if proven that the voltage peaks on the connection terminals of the fan are inside stress ca...

Страница 13: ...maintenance troubleshooting cleaning and service Observe 5 safety rules for the electrical expert disconnect from the power supply all pole prevent switching on again test absence of voltage earthing...

Страница 14: ...The actual pressure drop of the system is higher than supposed the fan could operate in an unsta ble area of the fan curve Check operating point and system design Consult cus tomer service of the man...

Страница 15: ...tem from control panel as well as signal lights Test of hatch opening closing Check the joints of actuator and hatch cover are properly fastened Check if smoothly opens closes Check the safety measure...

Страница 16: ...ng Dismount carefully WARNING Hazard from falling parts When selecting the hoisting device observe the weight weight information on the name plate Carefully disconnect all wires Remove the fan from du...

Страница 17: ...DVV 16 08 2021 17 Appendix 1 Dimensions...

Страница 18: ...18 DVV 16 08 2021 Appendix 2 Installation examples...

Страница 19: ...rn the cooling ducts towards each other 2 Mount the fan on the horizontal base base pitch 10 mm m 3 Don t fix the cable on the casing 4 Enable free cooling air inlet and free outlet DVV F400 shown App...

Страница 20: ...eq con operation marking EMC See IMO Chapter 7 Prewired in D inside fan P2 18 5 kW All wires led out to service switch to connect in D on site P2 22 kW 95492 DVV 1000D4 XM F400 IE2 EMC 95448 DVV 1000D...

Страница 21: ...ply d max 10 mmq D max 18 mm 2 M16x1 5 PTC d max 1 5 mmq D max 10 mm 3 M32x1 5 M40x1 5 1 2 3 1 2 3 1 2 3 DVV 800D4 XS 4 6 XS DVV 800D6 8 XL DVV 1000D6 XL 6 XP DVV 1000D6 8 XL 6 12 XL DVV 800D4 XL 4 6...

Страница 22: ...hinery Electrical equipment of machines Part 1 General requirements EN 12101 3 Smoke and heat control systems part 3 Specification for powered smoke and heat exhaust ven tilators complies with the pro...

Страница 23: ...o prevent hazard zones being reached by upper and lower limbs EN 60204 1 Safety of machinery Electrical equipment of machines Part 1 General requirements Note1 Compliance with EC Machinery Directive a...

Страница 24: ...achinery Electrical equipment of machines Part 1 General requirements EN 12101 3 Smoke and heat control systems part 3 Specification for powered smoke and heat exhaust ven tilators complies with the p...

Страница 25: ...istances to prevent hazard zones being reached by upper and lower limbs EN 60204 1 Safety of machinery Electrical equipment of machines Part 1 General requirements Note1 Compliance with Supply of Mach...

Отзывы: