background image

The remote fault LED will blink the set sensitivity of the detector. The
number of blinks, similar to number of blinks from the arrows, will represent
the set sensitivity and the sequence is repeated every 3 seconds till the
detector is reset.

The LEDs at the remote test station will mimic the detector front LEDs.

Note:

For the OSI-RIE-xx this test does not satisfy the requirements

of NFPA72 for periodic maintenance and sensitivity verification
of beam type detectors.

For the OSI- RIE- xx this test in conjunction with the complete reflector
blockage test (see step 4 of the Installation/Alignment procedure in this
manual) does satisfy the requirements of NFPA72 for periodic maintenance
and sensitivity verification of beam type detectors.

If the detector fails this test several steps should be taken to determine if the
detector is faulty or simply needs to be re-adjusted before returning the unit
for repair. These steps include:

1.

Verify all wiring connections and appropriate power is applied to the
detector.

2.

Verify that the optical line of sight is free from obstructions and
reflective objects.

3.

Apply the maintenance procedure in this manual. Repeat the test
procedure. If the detector still fails the test procedure proceed with step
4.

4.

Repeat the alignment procedure in this manual. If the alignment
procedure is successful repeat the test procedure. If the detector still
fails the test it should be returned.

Detectors

must

be

tested

after

installation

and

following

periodic

maintenance.

Congratulations. You have completed the final installation and alignment
procedure.

Operation After A Power Failure

The detector has the reflector location/position, set sensitivity and other
commissioning parameters permanently memorised after the initialisation
process.

After a power failure of any duration, when the supply is restored the detector
will check the possible new situation versus it memorised data.

If the reflector is found in the same position and all parameters are within
acceptable limits, the detector will resume its operation and go out of fault
condition.

If any significant parameters have changed, it will remain in a fault condition
and a re-initialisation will be required.

Maintenance

Note:

Before cleaning the detector, notify the proper authorities that

the smoke detector system is undergoing maintenance, and
therefore the system will be temporarily out of service. Disable
the zone or system undergoing maintenance to prevent unwanted
alarms.

1.

Carefully clean the outer housing lens face. A damp soft cloth with a
mild soap may be used. Avoid products with solvents or ammonia.

2.

Carefully clean the reflector. A damp soft cloth with a mild soap may
be used. Avoid products with solvents or ammonia.

3.

Notify the proper authorities that the system is back on line.

Painting

The outer aesthetic ring may be painted using a spray or brush type paint of
appropriate type. For more information refer to section Specifications.

Note:

Never paint the flat lens surface of the imager.

Special

Note

Regarding

Smoke

Detector Guards

Smoke detectors are not to be used with detector guards unless the
combination has been evaluated and found suitable for that purpose.

13

E56-6965-000

Содержание OSI-RIE Series

Страница 1: ...ailable from System Sensor All proper health and safety precautions must be taken during the installation commissioning and maintenance of the product The system should not be connected to a power sou...

Страница 2: ...any provision outlined above is found to be invalid or unenforceable by a court of law such invalidity or unenforceability will not affect the remainder which will continue in full force and effect Al...

Страница 3: ...o section Humidity 0 to 95 RH Non condensing Mechanical Value Shipping Weight Complete unit 3 91 lbs 1 77kg Shipping Size 10 7 8 X 8 7 8 X 7 26 28 cm x 21 2 cm x17 78 cm Mounting Wall only without opt...

Страница 4: ...4 E56 6965 000 Dimensions Figure 3 1 Detector dimensions...

Страница 5: ...5 E56 6965 000 140 mm Figure 3 2 Reflector dimensions...

Страница 6: ...he conditions above can be addressed or minimized Some examples of applications for beam detectors might include aircraft hangars cold storage warehouses shipping warehouses enclosed parking facilitie...

Страница 7: ...sidewall may be used as a guide See Figure 3 3 The beam detector can be mounted with the transmitter receiver on one wall and the reflector on the opposite wall or both suspended from the ceiling or a...

Страница 8: ...uisance alarm or trouble conditions Initial selection of a proper mounting surface will eliminate false alarms and nuisance trouble signals Mount the detector on a stable mounting surface such as bric...

Страница 9: ...jects such as ductwork or windows should be a minimum 2 out of the center of the beam path of the beam In cases where reflective objects cannot be avoided the complete reflector blockage test can be u...

Страница 10: ...hen using one of the optional remote test stations Figure 3 16 shows the remote outputs for trouble and alarm Warning Disable the zone or system before applying power to the beam detector to prevent u...

Страница 11: ...to confirm that there are no obstructions or reflective objects within 15 38 1cm of the beam s path Insert the OSP 002 in the slot provided in the eyeball at 06 00 and move the eyeball The eyeball mo...

Страница 12: ...oing maintenance to prevent unwanted alarms Before testing the detector check for the presence of the flashing green OK LED at the receiver making sure not to disturb or block the beam If it does not...

Страница 13: ...nce Congratulations You have completed the final installation and alignment procedure Operation After A Power Failure The detector has the reflector location position set sensitivity and other commiss...

Страница 14: ...Station l Blinks till reset from FACP Trouble Drift Compensation Off 3 Quick Blinks Blink Long Term Drift Reference Out of 20 Range l Reduced IR Signal l Clean detector and reflector Trouble Beam Bloc...

Страница 15: ...uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that...

Страница 16: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Compa...

Отзывы: