E56-6965-000

Appendix I. Operation Modes and Troubleshooting Guide OSI-RIE-xx:

Modes

Red and Remote
Alarm Output

Yellow and
Remote Trouble
Output

Green

Initiating means

Comments and Troubleshooting Tips

Power On

Off

Blink

Off

Apply Power from discharged state.

l

All wiring correctly done.

l

Address switches set.

Alignment

Off

Blink

Off

Lever in 3:00 position and
commissioning is active.

l

Ready to perform alignment.

l

Follow guidance from the 4 arrows to
correctly align.

Initializing/
Commissioning

Off

Blink

Off

Lock lever in 6:00 position to start
commissioning.

l

Commissioning and setting sensitivity.

l

Do not interrupt beam.

Normal

Off

Off

Blink

Successful completion of
initialization or detector reset.

l

Initializing finished.

l

Detector operates normal in quiescent
condition.

l

Detector successfully reset.

Alarm

On

Off

Off

Smoke, Test Filter or RTS151KEY
Test Station.

l

Blinks till reset from FACP .

Trouble-Drift
Compensation

Off

3 Quick Blinks

Blink

Long Term Drift Reference Out of
20% Range.

l

Reduced IR Signal.

l

Clean detector and reflector.

Trouble-Beam
Blockage

Off

4 Quick Blinks

Blink

Beam blockage or detector out of
alignment.

l

Remove blockage or re-align detector.

l

Faulty unit.

Trouble-Imager
saturation

Off

5 Quick Blinks

Blink

Imager saturated.

l

Sunlight or very strong light into
detector or reflector.

l

Re-position detector or reflector.

l

Remove light source.

Test activated-Pass
Result

On

Blinks the set
sensitivity by
number of blinks
(1-4). Repeats
every 3 seconds
till reset.

Off

FACP or RTS151KEY.

l

Remains in alarm until reset by FACP.

l

Number of lit arrows indicates
sensitivity level that was selected
automatically.

Blink patterns

1.

OK/Green:

l

Imager will flash green once every 5 seconds.

2.

Alarm/Red:

l

Imager red solid on.

3.

Faults/Yellow:

l

Number of pulses identifies type of fault.

l

Rhythm; every pulse 15ms ON/15ms OFF, repeat after 2 seconds till fault has disappeared.

l

Blinks only highest priority fault.

Содержание OSI-RIE Series

Страница 1: ...ailable from System Sensor All proper health and safety precautions must be taken during the installation commissioning and maintenance of the product The system should not be connected to a power sou...

Страница 2: ...any provision outlined above is found to be invalid or unenforceable by a court of law such invalidity or unenforceability will not affect the remainder which will continue in full force and effect Al...

Страница 3: ...o section Humidity 0 to 95 RH Non condensing Mechanical Value Shipping Weight Complete unit 3 91 lbs 1 77kg Shipping Size 10 7 8 X 8 7 8 X 7 26 28 cm x 21 2 cm x17 78 cm Mounting Wall only without opt...

Страница 4: ...4 E56 6965 000 Dimensions Figure 3 1 Detector dimensions...

Страница 5: ...5 E56 6965 000 140 mm Figure 3 2 Reflector dimensions...

Страница 6: ...he conditions above can be addressed or minimized Some examples of applications for beam detectors might include aircraft hangars cold storage warehouses shipping warehouses enclosed parking facilitie...

Страница 7: ...sidewall may be used as a guide See Figure 3 3 The beam detector can be mounted with the transmitter receiver on one wall and the reflector on the opposite wall or both suspended from the ceiling or a...

Страница 8: ...uisance alarm or trouble conditions Initial selection of a proper mounting surface will eliminate false alarms and nuisance trouble signals Mount the detector on a stable mounting surface such as bric...

Страница 9: ...jects such as ductwork or windows should be a minimum 2 out of the center of the beam path of the beam In cases where reflective objects cannot be avoided the complete reflector blockage test can be u...

Страница 10: ...hen using one of the optional remote test stations Figure 3 16 shows the remote outputs for trouble and alarm Warning Disable the zone or system before applying power to the beam detector to prevent u...

Страница 11: ...to confirm that there are no obstructions or reflective objects within 15 38 1cm of the beam s path Insert the OSP 002 in the slot provided in the eyeball at 06 00 and move the eyeball The eyeball mo...

Страница 12: ...oing maintenance to prevent unwanted alarms Before testing the detector check for the presence of the flashing green OK LED at the receiver making sure not to disturb or block the beam If it does not...

Страница 13: ...nce Congratulations You have completed the final installation and alignment procedure Operation After A Power Failure The detector has the reflector location position set sensitivity and other commiss...

Страница 14: ...Station l Blinks till reset from FACP Trouble Drift Compensation Off 3 Quick Blinks Blink Long Term Drift Reference Out of 20 Range l Reduced IR Signal l Clean detector and reflector Trouble Beam Bloc...

Страница 15: ...uses and can radiate radio frequency energy and if not installed and used in accordance with the instructions may cause harmful interference to radio communications However there is no guarantee that...

Страница 16: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Compa...

Отзывы: