[5.8] Install The Cover 

Install the cover using the six screws that are captured in 
the housing cover. Be certain filters are installed as speci-
fied in Section [5.5]. Make sure that the cover fits into the 
base  groove  and  that  all  gaskets  are  in  their  proper  posi-
tions. Tighten the six screws.

[6] Duct Smoke Detector Maintenance And Test 
Procedures

Test and maintain duct smoke detectors as recommended 
in  NFPA  72.  The  tests  contained  in  this  manual  were 
devised to assist maintenance personnel in verification of 
proper detector operation. 

Before conducting these tests, notify the proper authorities 
that the smoke detection system will be temporarily out of 
service. Disable the zone or system under test to prevent 
unwanted alarms.

[6.1] Smoke Entry Tests
[6.1.1] Air Flow

The DH100ACDCLPX is designed to operate over an extended 
air speed range of 100 to 4000 FPM. To verify sufficient sam-
pling of ducted air, turn the air handler on and use a manom-
eter  to  measure  the  differential  pressure  between  the  two 
sampling  tubes.  The  differential  pressure  should  measure 
at least 0.0015 inches of water and no more than 1.2 inches 
of water. Because most commercially available manometers 
cannot  accurately  measure  very  low  pressure  differentials, 
applications with less than 500 FPM of duct air speed may 
require one of the following: 1) the use of a current-sourcing 
pressure transmitter (Dwyer Series 607) per Section 6.1.4 or; 
2) the use of aerosol smoke per section 6.1.2.

[6.1.2] Air Flow Test using Aerosol Smoke

This test is intended for low-flow systems (100-500FPM). If 
the air speed is greater than 500 FPM, use a conventional 
manometer  to  measure  differential  pressure  between  the 
sampling tubes as described in 6.1.1.

Drill a 

1

4

 hole 3 feet upstream from the duct smoke detec-

tor. With the air handler on, measure the air velocity with 
an anemometer. Air speed must be at least 100 FPM.

 

Spray 

aerosol smoke* into the duct through the 

1

4

 hole for five 

seconds. Wait two minutes for the duct smoke detector to 
alarm.  If  the  duct  smoke  detector  alarms,  air  is  flowing 
through the detector. Remove the duct smoke detector cover 
and blow out the residual aerosol smoke from the chamber 
and reset the duct smoke detector. Use duct tape to seal the 
aerosol smoke entry hole.

*Aerosol  smoke  can  be  purchased  from  Home  Safeguard  Industries, 

Malibu, CA. Phone: 310/457-5813.

[6.1.3] Smoke Entry Test

To  determine  if  smoke  is  capable  of  entering  the  sens-
ing  chamber,  visually  identify  any  obstructions.  Plug  the 
exhaust  and  inlet  tube  holes  to  prevent  ducted  air  from 

carrying  smoke  away  from  the  detector  head,  then  blow 
smoke  such  as  cigarette,  cotton  wick,  or  punk  directly  at 
the head to cause an alarm. REMEMBER TO REMOVE THE 
PLUGS AFTER THIS TEST, OR THE DETECTOR WILL NOT 
FUNCTION PROPERLY.

[6.1.4] Air Flow Test using Dwyer Series 607 
Differential Pressure Transmitter

Verify the air speed of the duct using an anemometer. Air 
speed must be at least 100 FPM. Wire the Dwyer transmit-
ter as shown in Figure 6. Connect the leads of the meter 
to either side of the 1000

Ω

 resistor. Allow unit to warm up 

for 15 seconds. With both HIGH and LOW pressure ports 
open  to ambient air, measure and record the voltage drop 
acrossthe  1000

Ω

  resistor  (measurement  1),  4.00  volts  is 

typical. Using flexible tubing and rubber stoppers, connect 
the HIGH side of the transmitter to the inlet sampling tube 
of the duct smoke detector housing, and the LOW side of 
the  transmitter  to  the  exhaust  sampling  tube  of  the  duct 
smoke  detector  housing.  Measure  and  record  the  voltage 
drop across the 1000

Ω

 resistor (measurement 2). Subtract 

the  voltage  recorded  in  measurement  1  from  the  voltage 
recorded in measurement 2. If the difference is greater than 
0.15 volts, there is enough air flow through the duct smoke 
detector for proper operation.

Figure 6. Procedure for verifying air flow:

DIFFERENTIAL

PRESSURE

TRANSMITTER

MODEL #607-01

HIGH

LOW

TO SAMPLING TUBE

TO EXHAUST TUBE

VOLT METER

FLUKE MODEL 87

OR EQUIVALENT

1000 OHM 5% 1 WATT RESISTOR

9 VOLT

BATTERY

9 VOLT

BATTERY

9 VOLT

BATTERY

15 TO 36VDC

SUPPLY

H0163-01

[6.1.5] Filter Replacement

The  filters  do  not  substantially  affect  smoke  performance 
even  when  up  to  90%  of  the  filter  is  clogged.  Quarterly 
visual inspection usually suffices to determine whether the 
filters should be replaced because only a high percentage 
of contamination affects performance. If further testing is 
required, compare  differential pressure readings with and 
without the filters installed. If the difference exceeds 10% 
replace the filters. In no case should the pressure differen-
tial fall below 0.0015 inches of water.

[6.2] Standby, Alarm and Sensitivity Tests

The cover must be removed to perform these tests. The use 
of a remote accessory for visible indication of power and 
alarm is recommended.

D200-33-00                                                                                              4                                                                                              I56-1944-07

Содержание Innovair DH100ACDCLPX

Страница 1: ...the management of toxic smoke and fire gases throughout the areas served by the duct system The DH100ACDCLPX detector is designed to operate on 24 VDC VAC Alarm and supervisory relay contacts are ava...

Страница 2: ...product For optimal performance it is recommended that the sampling tube extend at least 2 3 of the way across the duct width Table 1 Sampling Tube Lengths Approximate Length Part Number to Order Repl...

Страница 3: ...ccumulated Visually inspect the filters at least quarterly inspect them more often if the dust accumulation warrants it See Section 6 for more information Replacement filters can be ordered from Syste...

Страница 4: ...Home Safeguard Industries Malibu CA Phone 310 457 5813 6 1 3 Smoke Entry Test To determine if smoke is capable of entering the sens ing chamber visually identify any obstructions Plug the exhaust and...

Страница 5: ...ER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISO...

Страница 6: ...cessories are used with the DH100 Series detectors The functionality of the magnetic coil has been designed into the circuitry of the new Innovair duct smoke detec tors 6 2 2 3 SSK451 Multi Signaling...

Страница 7: ...tage 20 29 VDC 24 VAC 50 60 Hz Input capacitance 270 F max Reset voltage 3 0 VDC min 2 0 VAC min Reset time with RTS451 03 to 0 3 sec Reset time by power down 0 6 sec max Power up time 34 sec max Alar...

Страница 8: ...D200 33 00 8 I56 1944 07 2003 System Sensor...

Страница 9: ...D200 33 00 9 I56 1944 07 2003 System Sensor...

Страница 10: ...D200 33 00 10 I56 1944 07 2003 System Sensor...

Страница 11: ...gned to protect property not life Warning devices including horns sirens and bells may not alert people or wake up sleepers who are located on the other side of closed or partially open doors A warnin...

Страница 12: ...ication devices including sirens bells horns and or strobes In residential applica tions each automatic alarm initiating device when activated shall cause the operation of an alarm notification device...

Отзывы: