Figure 3. Air duct detector sampling tube:
SAMPLING
TUBE
END
CAP
AIR HOLES
STOP SCREW
MOUNTING HOLES
AT 90
°
INCREMENTS
AIR FLOW DIRECTION
H0171-00
Sampling tubes for this product are designed to be inserted
from the outside, without removing the cover, prior to
installing the detector into its application.
1. Install the end cap into the end of the tube farthest from
the stop screw.
2. Slide the tube into whichever bushing will be used for the
air inlet, and push it all the way to the stop. The end of
the tube with the four small holes goes into the bushing.
3. Rotate the tube so that the holes face into the airflow,
then adjust until the hole in the bushing lines up with
one of the four mounting holes in the tube.
4. Secure the tube by inserting a #6 ×
3
⁄
4
˝ sheet metal
screw through the hole in the bushing and the mounting
hole in the tube. See Figure 4.
Figure 4. Sampling tube connected to duct smoke
detector:
A78-2752-00
[5.4] Install the Detector Housing
Feed the sampling tube and the exhaust port through the pre-
drilled holes in the mounting location, then use two screws
to secure the housing to the mounting surface.
Caution: Do not overtighten the screws.
[5.5] Air Filters
Air filters must be installed in both the inlet and exhaust
openings inside the detector. These filters are initially
installed at the factory. To remove for cleaning. loosen the
holding tab and pull the filter out. Replace the filters by
pushing them into the sampling and exhaust tube holes, as
shown in Figure 5, then replacing the holding tabs.
D200-33-00 3 I56-1944-07
Figure 5. Sampling tube filter installation:
CAUTION
Filters require periodic cleaning or replacement, depend-
ing on the amount of dust and dirt accumulated. Visually
inspect the filters at least quarterly; inspect them more
often if the dust accumulation warrants it. See Section [6]
for more information. Replacement filters can be ordered
from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174.
(Exhaust tube/intake tube filter P/N F36-09-11)
[5.6] Field Wiring
Installation Guidelines
All wiring must be installed in compliance with the
National Electrical Code and the local codes having juris-
diction. Proper wire gauges should be used. The conduc-
tors used to connect smoke detectors to control panels and
accessory devices should be color-coded to prevent wiring
mistakes. Improper connections can prevent a system from
responding properly in the event of a fire.
For signal wiring, (the wiring between interconnected
detectors or from detectors to auxiliary devices), it is
usually recommended that single conductor wire be no
smaller than 18 gauge. The duct smoke detector terminals
accommodate wire sizes up to 12 gauge.
Smoke detectors and alarm system control panels have
specifications for allowable loop resistance. Consult the
control panel manufacturer’s specifications for the total
loop resistance allowed for the particular model control
panel being used before wiring the detector loop.
Wiring Instructions
The DH100ACDCLPX detectors are designed for easy wir-
ing. The housing provides a terminal strip with clamping
plates. Wiring connections are made by stripping about
3
⁄
8
″
of insulation from the end of the wire, sliding the bare end
under the plate, and tightening the clamping plate screw.
[5.7] Perform Detector Check
1. Perform STANDBY AND TROUBLE TEST per Section
[6.2.1].
2. Perform MAGNET TEST per Section [6.2.2.1]. The
RTS451 test of Section [6.2.2.2] may substitute for this
requirement.
3. Perform AIR FLOW TEST per Section [6.1.1].
4. Perform SMOKE RESPONSE TEST per Section [6.1.2].
5. Perform SENSITIVITY TEST per Section [6.2.3].