System Sensor Innovair DH100ACDCLPX Скачать руководство пользователя страница 3

Figure 3. Air duct detector sampling tube:

SAMPLING

TUBE

END

CAP

AIR HOLES

STOP SCREW

MOUNTING HOLES

AT 90

°

 INCREMENTS

AIR FLOW DIRECTION

H0171-00

Sampling tubes for this product are designed to be inserted 
from  the  outside,  without  removing  the  cover,  prior  to 
installing the detector into its application.
1. Install the end cap into the end of the tube farthest from 

the stop screw.

2. Slide the tube into whichever bushing will be used for the 

air inlet, and push it all the way to the stop. The end of 
the tube with the four small holes goes into the bushing. 

3. Rotate the tube so that the holes face into the airflow, 

then adjust until the hole in the bushing lines up with 
one of the four mounting holes in the tube.

4. Secure  the  tube  by  inserting  a  #6  × 

3

4

˝  sheet  metal 

screw through the hole in the bushing and the mounting 
hole in the tube. See Figure 4.

Figure 4. Sampling tube connected to duct smoke 
detector:

A78-2752-00

[5.4] Install the Detector Housing

Feed the sampling tube and the exhaust port through the pre-
drilled holes in the mounting location, then use two screws 
to secure the housing to the mounting surface.

Caution: Do not overtighten the screws.

[5.5] Air Filters 

Air filters must be installed in both the inlet and exhaust 
openings  inside  the  detector.  These  filters  are  initially 
installed at the factory. To remove for cleaning. loosen the 
holding  tab  and  pull  the  filter  out.  Replace  the  filters  by 
pushing them into the sampling and exhaust tube holes, as 
shown in Figure 5, then replacing the holding tabs.

D200-33-00                                                                                              3                                                                                              I56-1944-07

Figure 5. Sampling tube filter installation:
                                           

                                           

CAUTION

Filters  require  periodic  cleaning  or  replacement,  depend-
ing on the amount of dust and dirt accumulated. Visually 
inspect  the  filters  at  least  quarterly;  inspect  them  more 
often if the dust accumulation warrants it. See Section [6] 
for  more  information.  Replacement  filters  can  be  ordered 
from System Sensor, 3825 Ohio Ave., St. Charles, IL 60174. 
(Exhaust tube/intake tube filter P/N F36-09-11)

[5.6] Field Wiring
Installation Guidelines

All  wiring  must  be  installed  in  compliance  with  the 
National Electrical Code and the local codes having juris-
diction. Proper wire gauges should be used. The conduc-
tors used to connect smoke detectors to control panels and 
accessory devices should be color-coded to prevent wiring 
mistakes. Improper connections can prevent a system from 
responding properly in the event of a fire.

For  signal  wiring,  (the  wiring  between  interconnected 
detectors  or  from  detectors  to  auxiliary  devices),  it  is 
usually  recommended  that  single  conductor  wire  be  no 
smaller than 18 gauge. The duct smoke detector terminals 
accommodate wire sizes up to 12 gauge.

Smoke  detectors  and  alarm  system  control  panels  have 
specifications  for  allowable  loop  resistance.  Consult  the 
control  panel  manufacturer’s  specifications  for  the  total 
loop  resistance  allowed  for  the  particular  model  control 
panel being used before wiring the detector loop. 

Wiring Instructions 

The  DH100ACDCLPX  detectors  are  designed  for  easy  wir-
ing.  The  housing  provides  a  terminal  strip  with  clamping 
plates.  Wiring connections are made by stripping about 

3

8

 

of insulation from the end of the wire, sliding the bare end 
under the plate, and tightening the clamping plate screw. 

[5.7] Perform Detector Check 

1. Perform  STANDBY  AND  TROUBLE  TEST  per  Section 

[6.2.1].

2. Perform  MAGNET  TEST  per  Section  [6.2.2.1].  The 

RTS451 test of Section [6.2.2.2] may substitute for this 
requirement. 

3. Perform AIR FLOW TEST per Section [6.1.1].
4. Perform SMOKE RESPONSE TEST per Section [6.1.2].
5. Perform SENSITIVITY TEST per Section [6.2.3].

H0131-00

Содержание Innovair DH100ACDCLPX

Страница 1: ...the management of toxic smoke and fire gases throughout the areas served by the duct system The DH100ACDCLPX detector is designed to operate on 24 VDC VAC Alarm and supervisory relay contacts are ava...

Страница 2: ...product For optimal performance it is recommended that the sampling tube extend at least 2 3 of the way across the duct width Table 1 Sampling Tube Lengths Approximate Length Part Number to Order Repl...

Страница 3: ...ccumulated Visually inspect the filters at least quarterly inspect them more often if the dust accumulation warrants it See Section 6 for more information Replacement filters can be ordered from Syste...

Страница 4: ...Home Safeguard Industries Malibu CA Phone 310 457 5813 6 1 3 Smoke Entry Test To determine if smoke is capable of entering the sens ing chamber visually identify any obstructions Plug the exhaust and...

Страница 5: ...ER INPUTS ALARM AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC 16 6 17 7 18 8 N C C N O N O C N C ALARM AUXILIARY CONTACTS SHOWN IN STANDBY CONTACTS TRANSFER DURING ALARM AS INDICATED BY THE ARROWS SUPERVISO...

Страница 6: ...cessories are used with the DH100 Series detectors The functionality of the magnetic coil has been designed into the circuitry of the new Innovair duct smoke detec tors 6 2 2 3 SSK451 Multi Signaling...

Страница 7: ...tage 20 29 VDC 24 VAC 50 60 Hz Input capacitance 270 F max Reset voltage 3 0 VDC min 2 0 VAC min Reset time with RTS451 03 to 0 3 sec Reset time by power down 0 6 sec max Power up time 34 sec max Alar...

Страница 8: ...D200 33 00 8 I56 1944 07 2003 System Sensor...

Страница 9: ...D200 33 00 9 I56 1944 07 2003 System Sensor...

Страница 10: ...D200 33 00 10 I56 1944 07 2003 System Sensor...

Страница 11: ...gned to protect property not life Warning devices including horns sirens and bells may not alert people or wake up sleepers who are located on the other side of closed or partially open doors A warnin...

Страница 12: ...ication devices including sirens bells horns and or strobes In residential applica tions each automatic alarm initiating device when activated shall cause the operation of an alarm notification device...

Отзывы: