background image

D200-101-00

8

I56-3888-105  

Password Sequence to Enter 

Maintenance

 Mode

Press  and  hold 

RESET

;  Left  flow  indicator  will  turn  yellow,  then 

green.
Release 

RESET

 and 

FAULT

 indicator will switch on green. The 

left flow indicator will blink green indicating the device is ready for 

the first digit.
Press 

DISABLE

 to increment the LEDs 1…9; press 

TEST

 to select 

a digit.

The  flashing  airflow  segment  will  turn  solid  green  and  the  next 

segment will begin to flash indicating set the next digit. When the 

4th digit is selected, all 4 airflow segments are turned off. If the 

password is accepted the 

FAULT

 indicator will remain green and 

the unit enters 

Maintenance

  mode.  If  the  password  is  incorrect 

the 

FAULT

 indicator flashes yellow and the unit remains in 

Normal

 

mode. The Default password in 

3111

.

If no button is pressed for 10s during the password sequence, the 

unit returns to 

Normal

 mode. 

Exit from Maintenance Mode

To exit from the 

Maintenance

 mode, press the three front panel 

user interface buttons 

TEST

RESET

 and 

DISABLE

 simultaneously 

for 2 seconds. Alternatively, reset the unit using the 

Remote Input

 

(when set to default value) or power the device off and on again.

If there is no activity in 

Maintenance

 mode for 5 minutes (default), 

the 

FAULT

 indicator blinks green for 15s and then the unit 

automatically returns to the 

Normal

 state.

TESTING
Magnet Test

The alarm signalling can be tested for functionality by placing a 

test magnet in the position shown in Figure 9 (displayed earlier in 

the guide). This method does not test the air flow in the pipe-work.

Smoke Testing

The system alarm response can be tested for functionality 

using smoke. The choice of smoke source is dependant on the 

installation but in all cases the smoke must be present for the 

duration of the test. Smoke pellets or matches can be used close 

to the sampling point to introduce smoke particulates into the 

system. It is recommended that smoke with a particulate life cycle 

of greater than 120s should be used – standard aerosol sprays for 

point detector testing do not work well on aspirated systems.

Table 5: Front Panel Buttons

Fault Testing 

Simulate a fault on the detector (for example, block the outlet pipe) 

and check that a fault is signalled on both the front panel of the unit 

and at the CIE (Fire Panel).

SERVICE

WARNING

Isolate the aspirating detector from the fire alarm system to prevent 

any  unwanted  alarms  when  opening  the  front  door  of  the  unit. 

Make sure all power is removed from the system before removing 

any covers. 

Service Mode

Opening the cabinet door during normal operation will cause the 

unit to enter 

Service

 Mode. The 

FILTER

 LEDs will blink, the unit will 

switch off power to the fans and the fault relay will indicate a fault. 

When the cabinet door is closed, the unit restarts automatically.

Filters

Periodic cleaning or replacement of the filters will be required. 
The filters are located inside the cabinet at the top of the unit (see 

Figure 9 displayed earlier in the guide) and are removed as shown 

in the sequence below:

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

S

E

N

S

O

R

A

S

P

IR

A

T

O

R

D

R

IF

T

C

O

M

P

E

N

S

A

T

IO

N

TEMPERA

TURE

/

INPUT

DISABLE

/

SYSTEM

S

O

U

N

D

E

R

F

IL

T

E

R

L

O

W

F

L

O

W

H

IG

H

F

L

O

W

INITIALIZATION

LEVEL 1

SMOKE

FAULT

FAULT

POWER

LEVEL 2

SMOKE

INITIALIZATION

ALARM

PREALARM

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

 

F  i lters 

  

Either replace the filter assembly or carefully brush off the accumulated dust. 

Refit the filter, close and secure the cabinet door. The unit will initialise and restart. 

  

 

 

 

 

  

  

 

Smoke Sensors 

1

2

3

FOAM GASKET

BUTTON 

NORMAL Mode 

MAINTENANCE Mode 

RESET      

When pressed for 2 s, starts PASSWORD 

PROCEDURE to enter Maintenance 

mode.

When pressed for 2 s latched alarms, faults and 

sounders (relays) are reset 

 In DISABLE Mode, if pressed for 2 s unit will exit from 

DISABLE Mode but remains in MAINTENANCE Mode 

DISABLE  

Used to increment  Password digits in 

PASSWORD PROCEDURE

When pressed for 2 s, device enters DISABLE Mode 

for 60 minutes (default). (Alarms, alerts and faults not 

reported). 

(To exit DISABLE Mode see RESET) 

TEST         

Used to confirm password in PASSWORD 

PROCEDURE. Default Password = 3111

When pressed for 2 s and released, both sensors will 

simulate alarm 
When pressed for 4 s and released, sensor #1 will 

simulate alarm 
When pressed for 6 s and released, sensor #2 will 

simulate alarm 

Warning: Outputs will be activated by test

COMBINATIONS 

RESET + DISABLE 

When pressed for 2 s, shows fan speed 

(on smoke level scales) for a preset time. 

When pressed for 2 s, shows fan speed (on smoke 

level scales) for preset time. 

RESET + TEST 

No action 

When pressed for 2 s, turns off sounders 

RESET + TEST + DISABLE 

No action 

When pressed for 2 s, unit exits from MAINTENANCE 

Mode 

Содержание FAAST LT FL01 Series

Страница 1: ...to 93 non condensing IP Rating 65 Mechanical Exterior Dimensions See Figure 1 Wiring 0 5 mm to 2 mm max Maximum Single Pipe Length 100m Classes B C Maximum Branched Pipe Length 160m 2 x 80m Class C M...

Страница 2: ...e installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed Figure 6 Fasten the mounting bracket to the wall...

Страница 3: ...1 and or 2 6 FL0122E Channel 1 1 and or 2 Channel 2 3 and or 4 5 6 Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the p...

Страница 4: ...manufacturer PLACE WIRING LABEL HERE If the FAAST LT door is closed for a long time especially at high temperatures it may be necessary to use a flat bladed screwdriver between the two tabs at the top...

Страница 5: ...e LED and relay PRE ALARM 1 or 2 Set ON when PRE ALARM CONDITION is met on channel Default condition Level 1 FAULT 1 or 2 When FAULT CONDITION on Ch1 or Ch2 or a common FAULT occurs Fault is also indi...

Страница 6: ...F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER 2 10 3 1 4 5 6 7 8 9 TEMPERATURE INPUT S E N S O R A S P IR A T O R DR IFT CO MP EN SA TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L...

Страница 7: ...2 LOW FLOW ON Yellow Low flow fault Check filter check pipe network for blockages SENSOR 1 BLINK Yellow Sensor initialization fault Try to restart device Replace faulty sensor 2 BLINKS Yellow Sensor c...

Страница 8: ...ake sure all power is removed from the system before removing any covers Service Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will bl...

Страница 9: ...l phases of operation WARNING Using compressed air to clean the pipe system High pressure air flushed through the system could damage the fan ensure that the FAAST LT unit is sealed or detached from t...

Отзывы: