WIRING INSTALLATION

Power, Alarm and Control Connections

Figure 9: Inside the Detector

CHANNEL 2 FILTER

POWER AND 

ALARM 

CONNECTIONS

CHANNEL 1 FILTER

USB PORT

SENSOR      COVER

POSITION FOR

TEST MAGNET

Exhaust Pipe

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

5

6

EARTH BAR

MOUNT

EARTH BAR

MOUNT

F-LT-EB

EARTH BAR

(OPTIONAL)

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

3

4

Note 1: All wiring should comply with local 

requirements and regulations. 
Note 2: Panel wiring must observe the 

recommendations of the panel manufacturer

PLACE 

WIRING 

LABEL 

HERE

If the FAAST LT door is closed for a long time 

(especially at high temperatures) it may be 

necessary to use a flat-bladed screwdriver 

between the two tabs at the top of the unit to 

lever open the door (as shown above).

SAMPLING AREA

SAMPLING AREA

Whenever the FAAST LT is installed outside the risk area, return of 

the exhaust air back into the protected area can reduce flow faults 

due to pressure difference.

!

MODULE MOUNT

MODULE MOUNT

F-LT-PMB 

MODULE MOUNT 

KIT (OPTIONAL)*

*

If required, an input/output module 

can be installed into the FAAST LT 

unit. The optional module mount kit 

(F-LT-PMB) will be needed for this.

Содержание FAAST LT FL01 Series

Страница 1: ...to 93 non condensing IP Rating 65 Mechanical Exterior Dimensions See Figure 1 Wiring 0 5 mm to 2 mm max Maximum Single Pipe Length 100m Classes B C Maximum Branched Pipe Length 160m 2 x 80m Class C M...

Страница 2: ...e installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed Figure 6 Fasten the mounting bracket to the wall...

Страница 3: ...1 and or 2 6 FL0122E Channel 1 1 and or 2 Channel 2 3 and or 4 5 6 Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the p...

Страница 4: ...manufacturer PLACE WIRING LABEL HERE If the FAAST LT door is closed for a long time especially at high temperatures it may be necessary to use a flat bladed screwdriver between the two tabs at the top...

Страница 5: ...e LED and relay PRE ALARM 1 or 2 Set ON when PRE ALARM CONDITION is met on channel Default condition Level 1 FAULT 1 or 2 When FAULT CONDITION on Ch1 or Ch2 or a common FAULT occurs Fault is also indi...

Страница 6: ...F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER 2 10 3 1 4 5 6 7 8 9 TEMPERATURE INPUT S E N S O R A S P IR A T O R DR IFT CO MP EN SA TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L...

Страница 7: ...2 LOW FLOW ON Yellow Low flow fault Check filter check pipe network for blockages SENSOR 1 BLINK Yellow Sensor initialization fault Try to restart device Replace faulty sensor 2 BLINKS Yellow Sensor c...

Страница 8: ...ake sure all power is removed from the system before removing any covers Service Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will bl...

Страница 9: ...l phases of operation WARNING Using compressed air to clean the pipe system High pressure air flushed through the system could damage the fan ensure that the FAAST LT unit is sealed or detached from t...