background image

D200-101-00

5

I56-3888-105

Table 2: Wiring Terminal Designations

(Note - Terminals marked CH2 will only be available on 2 channel 

models)

Table 3: Relays

No.

Function

Ext Power In + 

 

Primary PSU  

T1

Ext Power In - 

 

Primary PSU  

Aux Power In + 

 

Not used in default 

Aux Power In  - 

 

Not used in default 

NC Alarm Relay  

CH1  

T2

C Alarm Relay  

CH1  

NO Alarm Relay  

CH1  

NC Alarm Relay  

CH2  

T3

C Alarm Relay  

CH2  

10 

NO Alarm Relay  

CH2  

11 

NC Fault Relay  

CH1  

T4

12 

C Fault Relay  

CH1  

13 

NO Fault Relay  

CH1  

14 

NC Fault Relay (AUX) 

CH2  

T5

15 

C Fault Relay (AUX) 

CH2  

16 

NO Fault Relay (AUX) 

CH2  

17 

Sounder Output 1 - 

47 k-ohm EOL Resistor 

T6 

18 

Sounder Output 1 + 

19 

Sounder Output 2 - 

47 k-ohm EOL Resistor 

T7 

20 

Sounder Output 2 +  

21 

Configurable Input + 

(Reset) Default is active = short circuit 

(unsupervised)

T8

22 

Configurable Input - 

(Reset)

23 

NC Pre-Alarm Relay  

CH1  

T9

24 

C Pre-Alarm Relay  

CH1  

25 

NO Pre-Alarm Relay   

CH1  

26 

NC Pre-Alarm Relay  

CH2  

T10

27 

C Pre-Alarm Relay  

CH2  

28 

NO Pre-Alarm Relay  

CH2  

RELAY 

ACTION: 

NOTES

ALARM 1 or 2 

Set ON when ALARM CONDITION is met 

on a channel  

Default condition = Level 1. Alarm state is 

latched as default.  A manual RESET is 

necessary to deactivate  LED and relay. 

PRE-ALARM 1 or 2  

Set ON when PRE-ALARM CONDITION 

is met on channel. 

Default condition = Level 1. 

FAULT 1 or 2 

When FAULT CONDITION on Ch1 or Ch2 

or a common FAULT occurs. Fault is also 

indicated when in SERVICE mode and 

when the unit is unpowered.  

Fault state is not latched (default) 

SOUNDER 1 or 2 

Set ON when a channel is in ALARM / 

PRE-ALARM. Sounder 1 corresponds to 

Ch1 and Sounder 2 corresponds to Ch2 

Default condition = set on in ALARM. 

Table 3a: Relay Electrical Specification

SPECIFICATION  MIN MAX 

UNITS 

COMMENTS 

Contact Rating 

 2 

0.5

A

A

30 VDC resistive load 

30 VAC resistive load 

Life Time 

10

5

   Operations 

 

1N6284CA

FAAST LT

FAAST LT

C

L

FAAST LT

R

L/C

WARNING: Switching Inductive Loads

Inductive loads can cause switching surges, which may damage 

the module relay contacts (see above).
To protect the relay contacts, connect a suitable Transient Voltage 

Suppressor (for example 1N6284CA ) across the load as shown.

Alternatively, for unsupervised DC applications, fit a diode with a 

reverse breakdown voltage greater than 10 times the circuit voltage

.

Fitting the Terminal Blocks

To insert the terminal blocks into the unit use the following method:

1  Insert a corner of the block into the slot (see 

a

).

2  Push the length of the block into the slot until the block ‘clicks’ 

into place, the 2 upper hooks on the block should be visible 

(see 

c

).

a

b

c

Содержание FAAST LT FL01 Series

Страница 1: ...to 93 non condensing IP Rating 65 Mechanical Exterior Dimensions See Figure 1 Wiring 0 5 mm to 2 mm max Maximum Single Pipe Length 100m Classes B C Maximum Branched Pipe Length 160m 2 x 80m Class C M...

Страница 2: ...e installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed Figure 6 Fasten the mounting bracket to the wall...

Страница 3: ...1 and or 2 6 FL0122E Channel 1 1 and or 2 Channel 2 3 and or 4 5 6 Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the p...

Страница 4: ...manufacturer PLACE WIRING LABEL HERE If the FAAST LT door is closed for a long time especially at high temperatures it may be necessary to use a flat bladed screwdriver between the two tabs at the top...

Страница 5: ...e LED and relay PRE ALARM 1 or 2 Set ON when PRE ALARM CONDITION is met on channel Default condition Level 1 FAULT 1 or 2 When FAULT CONDITION on Ch1 or Ch2 or a common FAULT occurs Fault is also indi...

Страница 6: ...F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER 2 10 3 1 4 5 6 7 8 9 TEMPERATURE INPUT S E N S O R A S P IR A T O R DR IFT CO MP EN SA TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L...

Страница 7: ...2 LOW FLOW ON Yellow Low flow fault Check filter check pipe network for blockages SENSOR 1 BLINK Yellow Sensor initialization fault Try to restart device Replace faulty sensor 2 BLINKS Yellow Sensor c...

Страница 8: ...ake sure all power is removed from the system before removing any covers Service Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will bl...

Страница 9: ...l phases of operation WARNING Using compressed air to clean the pipe system High pressure air flushed through the system could damage the fan ensure that the FAAST LT unit is sealed or detached from t...

Отзывы: