Figure 4: How to Knock Out Cable
Gland Holes
Figure 3: Remove Backing to
Stick Cover Down
When label
A
is in place, remove the protector from the bottom of
the clear cover to stick the cover down, as shown in Figure 3:
Cable Access
Knock out cable gland holes where required. The
location of the cable gland holes is shown in Figure 1,
represented by the icon:
This equipment and all associated pipe work must be installed in
accordance with all relevant codes and regulations.
PHYSICAL INSTALLATION
Front Panel Labels
The LT FL01 is shipped without the front panel labels fixed in place.
This allows the installer to choose the language required for the
installation from the Front Panel Labelling Pack.
Figure 2 shows where the labels need to be placed:
Figure 6: Fasten the mounting bracket to the wall
Mounting the LT FL01 to the Wall
Figure 2: Placing the Front Panel Labels
2
10
3
1
4
5
6
7
8
9
2
10
3
1
4
5
6
7
8
9
INPUT
SENSOR
ASPIRA
T
OR
E
L
B
A
SI
D
/
M
E
S
Y
TEMPER
A
TURE
SOUNDER
FIL
TER
LOW
FLOW
HIGH
FLOW
S
T
FAULT
POWER
LEVEL 2
SMOKE
MODULE 2
MODULE 1
LEVEL 1
SMOKE
FAULT
ALARM
PREALARM
A
Figure 5: Mounting Bracket
FAAST LT
HANGING LUGS
INDICATES CENTRE OF ASPIRATING PIPES
FIXING HOLE
FIXING HOLE
USE FOR PLUMB-LINE
90 mm
99 mm
59
329
212 mm
144 mm
41
mm
mm
mm
*
*
POSITION OF BRACKET
PLUMB LINE
BASE OUTLINE
OUTER DIMENSION OF UNIT
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17
18
* Minimum clearance required from hinges to open door = 35 mm.