D200-101-00

2

I56-3888-105  

Figure 4: How to Knock Out Cable 

Gland Holes

Figure 3: Remove Backing to 

Stick Cover Down

When label 

A

 is in place, remove the protector from the bottom of 

the clear cover to stick the cover down, as shown in Figure 3:

Cable Access

Knock  out  cable  gland  holes  where  required.    The 

location of the cable gland holes is shown in Figure 1, 

represented by the icon:

This equipment and all associated pipe work must be installed in 

accordance with all relevant codes and regulations.

PHYSICAL INSTALLATION

Front Panel Labels

The LT FL01 is shipped without the front panel labels fixed in place.  

This allows the installer to choose the language required for the 

installation from the Front Panel Labelling Pack.

Figure 2 shows where the labels need to be placed:

Figure 6: Fasten the mounting bracket to the wall

Mounting the LT FL01 to the Wall

Figure 2:  Placing the Front Panel Labels

2

10

3

1

4

5

6

7

8

9

2

10

3

1

4

5

6

7

8

9

INPUT

SENSOR

ASPIRA

T

OR

E

L

B

A

SI

D

/
M

E

S

Y

TEMPER

A

TURE

SOUNDER

FIL

TER

LOW

FLOW

HIGH

FLOW

S

T

FAULT

POWER

LEVEL 2

SMOKE

MODULE 2

MODULE 1

LEVEL 1

SMOKE

FAULT

ALARM

PREALARM

A

Figure 5: Mounting Bracket

FAAST LT

HANGING LUGS

INDICATES CENTRE OF ASPIRATING PIPES

FIXING HOLE

FIXING HOLE

USE FOR PLUMB-LINE

90 mm

99 mm

59

329

212 mm

144 mm

41

mm

mm

mm

*

*

POSITION OF BRACKET

PLUMB LINE

BASE OUTLINE

OUTER DIMENSION OF UNIT

1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17

18

* Minimum clearance required from hinges to open door = 35 mm.

Содержание FAAST LT FL01 Series

Страница 1: ...to 93 non condensing IP Rating 65 Mechanical Exterior Dimensions See Figure 1 Wiring 0 5 mm to 2 mm max Maximum Single Pipe Length 100m Classes B C Maximum Branched Pipe Length 160m 2 x 80m Class C M...

Страница 2: ...e installer to choose the language required for the installation from the Front Panel Labelling Pack Figure 2 shows where the labels need to be placed Figure 6 Fasten the mounting bracket to the wall...

Страница 3: ...1 and or 2 6 FL0122E Channel 1 1 and or 2 Channel 2 3 and or 4 5 6 Table 1 Pipe Holes Used for Each FAAST LT Model Note 1 Pipe holes not used should be kept sealed Note 2 Do NOT glue pipes into the p...

Страница 4: ...manufacturer PLACE WIRING LABEL HERE If the FAAST LT door is closed for a long time especially at high temperatures it may be necessary to use a flat bladed screwdriver between the two tabs at the top...

Страница 5: ...e LED and relay PRE ALARM 1 or 2 Set ON when PRE ALARM CONDITION is met on channel Default condition Level 1 FAULT 1 or 2 When FAULT CONDITION on Ch1 or Ch2 or a common FAULT occurs Fault is also indi...

Страница 6: ...F L O W INITIALIZATION LEVEL SMOKE FAULT FAULT POWER 2 10 3 1 4 5 6 7 8 9 TEMPERATURE INPUT S E N S O R A S P IR A T O R DR IFT CO MP EN SA TIO N DIS AB LE SY ST EM S O U N D E R F IL T E R L O W F L...

Страница 7: ...2 LOW FLOW ON Yellow Low flow fault Check filter check pipe network for blockages SENSOR 1 BLINK Yellow Sensor initialization fault Try to restart device Replace faulty sensor 2 BLINKS Yellow Sensor c...

Страница 8: ...ake sure all power is removed from the system before removing any covers Service Mode Opening the cabinet door during normal operation will cause the unit to enter Service Mode The FILTER LEDs will bl...

Страница 9: ...l phases of operation WARNING Using compressed air to clean the pipe system High pressure air flushed through the system could damage the fan ensure that the FAAST LT unit is sealed or detached from t...