background image

DUCTSD240 Duct Smoke Detector

INSTALLATION AND MAINTENANCE INSTRUCTIONS

 3825 Ohio Avenue, St. Charles, Illinois 60174

1-800-SENSOR2, FAX: 630-377-6495

www.systemsensor.com

TABLE OF CONTENTS 

PAGE

[1] Limitations of Duct Smoke Detectors. . . . . . . . . . . . . . . . . . . . . . . . . . 1
[2] Exploded View of Duct Smoke Detector Components   . . . . . . . . . . . . . 2
[3] General Description   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[4] Contents of Duct Smoke Detector Kit. . . . . . . . . . . . . . . . . . . . . . . . . . 2
[5] Detector Installation . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 2
[6] Sampling Tube Installation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[7] Measurement Tests . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 3
[8] Field Wiring Installation Guidelines. . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[9] Detector Status Indication. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4
[10] Interconnection (Multiple Fan Shut Down). . . . . . . . . . . . . . . . . . . . . 4
[11] Verification of Operation  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 5
[12] Detector Cleaning Procedures  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[13] Sensor Replacement  . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
[14] Optional Accessories. . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 6
Wiring Diagrams . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . 4-6
Detector Status   . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  7
Warranty . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . . .  8

 

BEFORE INSTALLING

Read System Sensor’s 

Applications Guide for Duct Smoke Detectors

 (HVAG53), 

which provides information on detector spacing, placement, zoning, wiring, 
and special applications. This manual is available online at www.systemsen-
sor.com. NFPA Standards 72 and 90A should also be referenced for detailed 
information. 

NOTICE:

 This manual shall be left with the owner/user of this equipment.

IMPORTANT:

 This detector must be tested and maintained regularly following 

NFPA 72 requirements. The detector should be cleaned at least once a year.

I56-4260-00

2R

SPECIFICATIONS

Operating Temperature: 

–4° to 158° F (–20° to 70° C)

Storage Temperature: 

–22° to 158° F (–30° to 70° C)

Humidity: 

0% to 95% Relative Humidity Non-condensing

Air Velocity: 

100 to 4000 ft./min. (0.5 to 20.3 m/sec.)

DUCTSD240 Footprint Dimensions:  Rectangular - 14.38 in L x 4.57 in W x 2.67 in D (37cm L x 11.6cm W x 6.8cm D)
 

Square - 7.75 in L x 9 in W x 2.67 in D (19.7cm L x 22.9cm W x 6.8cm D)

DUCTSD240 Weight: 

2.5 pounds; 1.14 kg

Electrical

Power supply voltage: 

20-29 VDC 

24 VAC 50-60-Hz 

240 VAC 50-60 Hz

Input capacitance: 

270 µF max. 

270 µF max. 

N/A

Reset Voltage: 

3.0 VDC min. 

2.0 VAC min. 

10 VAC min.

Reset Time (with RTS451/RTS151):  .03 to 0.3 sec. 

.03 to 0.3 sec. 

.03 to 0.3 sec.

Reset Time (by power down): 

0.6 sec. max. 

0.6 sec. max. 

0.6 sec. max.

Power Up Time: 

35 sec. max. 

35 sec. max. 

35 sec. max.

Alarm response time: 

15 sec. 

15 sec. 

15 sec.

Sensitivity Test: 

See detector label 

See detector label 

See detector label

Current Requirements (Using No Accessories)

Max. standby current 

21 mA @ 24 VDC 

65 mA RMS @ 24VAC 60Hz 

10 mA RMS @ 240 VAC 60 Hz

Max. alarm current 

65 mA @ 24 VDC 

135 mA RMS @ 24 VAC 60 Hz 

18 mA RMS @ 240 VAC 60 Hz

CONTACT RATINGS

Alarm initiation contacts (SPST)

2.0A @ 30 VDC (resistive)

Alarm auxiliary contacts (DPDT) 10A @30 VDC (resistive) 

10A @250 VAC (resistive)

1

/

2

 HP @240 VAC

1

/

4

 HP @120 VAC

NOTE: Alarm auxiliary contacts shall not be connected to initiating circuits of 

control panels. Use the alarm initiation contact for this purpose.

Supervisory Contacts (SPDT)

2.0A @ 30 VDC (resistive)
2.0A @ 125 VAC (resistive)

ACCESSORY CURRENT LOADS AT 24 VDC

DEVICE

STANDBY

TROUBLE

ALARM

APA151

12.5mA

n/a

30mA Max.

MHR/MHW

0mA

n/a

29mA Max.

RA100Z

0mA

n/a

12mA Max.

RTS151

0mA

n/a

12mA Max.

RTS151KEY

12mA

n/a

12mA Max.

NOTE: Any combination of accessories may be used such that the given  
accessory loads are: 110mA or less at the Aux output, and 50mA or less at the 
Alarm output.

[1] LIMITATIONS OF DUCT SMOKE DETECTORS 

WARNING

The National Fire Protection Association has established that DUCT DETEC-
TORS MUST NOT BE USED AS A SUBSTITUTE FOR OPEN AREA DETECTOR 
PROTECTION as a means of providing life safety. Nor are they a substitute for 
early warning in a building’s regular fire detection system.
System Sensor supports this position and strongly recommends that the user 
read NFPA Standards 90A, 72, and 101. The DUCTSD240 Air Duct Smoke De-
tectors are listed per UL 268A.
This device will not operate without electrical power. Fire situations may 
cause an interruption of power. The system safeguards should be discussed 
with your local fire protection specialist.
This device will not sense smoke unless the ventilation system is operating 
and the cover is installed.
For this detector to function properly, it MUST be installed according to the in-
structions in this manual. Furthermore, the detector MUST be operated within 
ALL electrical and environmental specifications listed in this manual. Failure 
to comply with these requirements may prevent the detector from activating 
when smoke is present in the air duct.

  

I56-4260-002R 

 

 06-10

Содержание DUCTSD240

Страница 1: ...5 sec max Alarm response time 15 sec 15 sec 15 sec Sensitivity Test See detector label See detector label See detector label Current Requirements Using No Accessories Max standby current 21 mA 24 VDC 65 mA RMS 24VAC 60Hz 10 mA RMS 240 VAC 60 Hz Max alarm current 65 mA 24 VDC 135 mA RMS 24 VAC 60 Hz 18 mA RMS 240 VAC 60 Hz CONTACT RATINGS Alarm initiation contacts SPST 2 0A 30 VDC resistive Alarm a...

Страница 2: ...hese parameters If neces sary use a velocity meter anemometer to check the air velocity in the duct 5 2 DETERMINE MOUNTING LOCATION AND CONFIGURATION On ducts wider than 18 inches it is recommended that the detector be mounted downstream of a bend obstruction in the duct or the supply or return air inlet Exception Installation of duct detectors can be on or within a commercial packaged rooftop hea...

Страница 3: ...ct Plug the end with the end cap and tape closed any holes in the protrud ing section of tube Be sure to seal the duct where the tube protrudes FIGURE 4 DETECTOR 3 4 HOLE 12 1 4 2 H0215 00 NOTE Air currents inside the duct may cause excessive vibration especially when the longer sampling tubes are used In these cases a 3 inch floor flange available at most plumbing supply stores may be used to fas...

Страница 4: ... WIRE DUCT SMOKE DETECTORS CAUTION Do not loop wire under terminals when wiring detectors Break wire runs to provide system supervision of connections 24VAC DC 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 16 6 17 8 18 7 N O C N C N O C N C 16 6 17 8 18 7 N O C N C N O C N C SUPERVISORY CONTACTS NOTE 3 24V 9 10 AUXILIARY CONTACTS FOR FAN SHUTDOWN ETC NOTE 2 SUPERVISORY CONTACTS NOTE 3 SUP N ...

Страница 5: ... REMEMBER TO REMOVE THE PLUGS AFTER THIS TEST OR THE DETECTOR WILL NOT FUNCTION PROPERLY FIGURE 8 MULTIPLE FAN SHUTDOWN INTERCONNECTION OF DUCTSD240 TO D4240 D4240 D4240 DUCTSD240 DUCTSD240 DUCTSD240 H0640 01 H0639 01 ALARM TEST OPTIONS TEST METHOD DETECTOR RESET Test Reset Button Press and hold test reset button for at least 7 seconds Press and release the test reset button Magnet Test M02 04 00 ...

Страница 6: ...If the smoke has cleared the unit will go into STANDBY otherwise the unit will remain in ALARM 12 DETECTOR CLEANING PROCEDURES Notify the proper authorities that the smoke detector system is undergoing maintenance and that the system will temporarily be out of service Disable the zone or system undergoing maintenance to prevent unwanted alarms and possible dispatch of the fire department 12 1 DETE...

Страница 7: ... green blink pattern exists until unit either enters Alarm or reverts to Standby within approximately 60 seconds Supervisory relay Terminals 3 and 14 are closed Alarm Relay Terminals 4 and 5 are open Aux Relay does not switch states Terminals 6 and 16 are closed Terminals 8 and 18 are closed Trouble Red Blink every 5 seconds Amber Solid Supervisory relay Terminals 3 and 14 are open Alarm Relay Ter...

Страница 8: ...tion number send defective units postage prepaid to Honeywell 12220 Rojas Drive Suite 700 El Paso TX 79936 USA Please include a note describing the malfunction and suspected cause of failure The Company shall not be obligated to replace units which are found to be defective because of damage unreasonable use modifications or alterations occurring after the date of manufacture In no case shall the ...

Отзывы: