background image

SS-400-012  9 I56-3749-006

FIGURE 14. BOTTOM VIEW OF UNIT

Wiring
Access

Plugs

Sampled

Air Inlet

Sampled

Air Outlet

Network

Connection

ASP03-00

WEB SERVER

The FAAST system contains an integrated Web server which is used to ob-
serve detector configuration and may be used to remotely monitor the unit.

The Web server features include:

•  Intuitive interface for remote monitoring of faults, relays, particulate 

level, air flow, and power supply

•  Facility location and contact information

•  Configuration settings display
•  Multi-Lingual support
•  Event log viewer

E-MAIL NOTIFICATION

The FAAST system has the ability to send e-mail notifications to an individual 
or organization. Up to 6 different email addresses may be stored for notifica-
tion. Each email address can be configured to be notified of a specific alarm 
level, fault level or isolate condition through the PipeIQ software. E-mails from 
the device indicate a device’s ID, location and alarm or fault type. A com-
prehensive networking guide may be downloaded at systemsensor.com/faast.

CANNED SMOKE TESTING

All FAAST systems must be tested after installation and periodically thereafter. 
Testing methods must statisfy the authority having jurisdiction. Systems of-
fer maximum performance when tested and maintained in compliance with 
CAN/ULC S536. UL Tested and approved aerosol smoke products are listed 
in Table 6.

MAINTENANCE

The only periodic maintenance required is to replace the filter assembly when 
the filter light is illuminated. Perform the following procedure to replace the 
filter assembly.

1.  Remove power from the system.
2.   Open the door on the right side of the device that covers the LED system 

indicators.

3.  Remove the plastic name card over the LEDs.
4.  Remove the two screws holding the filter assembly into the device.
5.  Remove the filter assembly and replace it with a new assembly.
6.   

Install the two screws to hold the filter assembly into the device. 

 

Torque the two Philips head screws to 6 in-lb (0.7 N-m) or 1/4 turn past 
“lightly snug”.  Do not over tighten.

7.  Replace the plastic name card over the LEDs.
8.  Close the door and return power to the system.

Other system checks may need to be performed in accordance with local or 
national codes and regulations.

CLASS I, DIVISION II

This equipment is suitable for use in Class I, Division 2, Class A, B, C and D 
OR non-hazardous environments only.

WARNING

EXPLOSION HAZARD - do not disconnect equipment unless power has been 
removed or the area is known to be non-hazardous

WARNING

EXPLOSION HAZARD - Substitution of any components may impair suitabil-
ity for Class I, Division 2

WARNING

Exposure to some chemicals may degrade the sealing properties of materials 
used in the relays.

ULC LISTED

COMPANY

AEROSOL

Home Safeguard

25S

No Climb

SOLOA4

SMOKE SABRE-01

TABLE 6. CANNED SMOKE TESTING

Содержание 8100A FAAST

Страница 1: ...s 5 26 kg includes packing material 8100A FAAST Fire Alarm Aspiration Sensing Technology 6581 Kitimat Rd Unit 6 Mississauga Ontario L5N 3T5 1 800 SENSOR2 Fax 905 812 0771 www systemsensor ca INSTALLATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS INTRODUCTION SCOPE OF THIS MANUAL 2 DESCRIPTION FEATURES 2 ITEMS INCLUDED WITH UNIT 2 INSTALLATION PIPE INSTALLATION 2 PHYSICAL UNIT INSTALLATION 2 S...

Страница 2: ...fe Electronic filter life monitoring Ultrasonic air flow sensing Field service access door Easy access filter maintenance door Event service and trend logs Pipe modeling software Acclimate mode operation for auto adjustment of sensitivity Remote monitoring via Ethernet IP Remote reset dry contact input Multi lingual support E mail notification of alarm fault or isolate conditions ITEMS INCLUDED WI...

Страница 3: ...me circumstances when it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit The output ports are tapered the same as the input ports to provide fast easy push fit connection of an exhaust pipe to the unit Perform the following pro cedure to connect the exhaust pipe to the unit 1 Square off and de burr the end of the exhaust pipe Ensure t...

Страница 4: ...ns to flow out of the exhaust port 6 Connect a computer with the PipeIQ software installed to the unit using the Ethernet connection on the bottom of the unit 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 When the configuration is complete remove the Ethernet connection to the unit USER INTERFACE The user interface shown in Figure 4 provides t...

Страница 5: ...l operation two adjacent indicators are green and correspond to the current air flow entering the detector When airflow is at a balanced level the two green segments are centered on the graph at levels 5 and 6 see Figure 7 As air flow rises and falls the green segments move right and left accordingly The segment on the far left represents a decrease in airflow of 20 Conversely movement to the segm...

Страница 6: ...he user interface when the button is enabled refer to pass code access section for activation details Test mode simulates a fire con dition activating all ten segments in the Particulate Level display and each segment in the Alarm display Each corresponding alarm relay is also acti vated after any programmed delay associated with that relay Activation of the RESET button removes the device from TE...

Страница 7: ...ESET button The first seg ment on the airflow display blinks green indicating the device is ready to accept the first digit To enter the passcode use the ISOLATE and TEST buttons shown in Figure 9 The ISOLATE button is used to increment the current digit As the current digit is incremented the segments of the Particulate Bar Graph illuminate accord ingly To complete entry of the digit press the TE...

Страница 8: ...etector events Up to 18 000 events can be stored Events that are tracked include alarms faults and user actions Event tracking data may be accessed via the network through the PipeIQ software or the Web server in terface Configuration and management of the log are done using the PipeIQ software Data Trend Log The FAAST system tracks trend data for each 24 hour time period up to 1 year The device r...

Страница 9: ...UL Tested and approved aerosol smoke products are listed in Table 6 MAINTENANCE The only periodic maintenance required is to replace the filter assembly when the filter light is illuminated Perform the following procedure to replace the filter assembly 1 Remove power from the system 2 Open the door on the right side of the device that covers the LED system indicators 3 Remove the plastic name card...

Страница 10: ...ess Contact information Date Wiring Checked Date Yes No Detector Settings Checked Date Yes No Test Relays Date Yes No REQUIRED DOCUMENTS Copy of Commissioning Form Yes No FAAST system Bill of Material Yes No Commissioning Form for each system Yes No Smoke Test results optional Yes No Locally required forms Yes No Customer s Signature Date Commissioning Agent Signature Date FAAST System Validation ...

Страница 11: ...y Yes No Is the pipe network installed and labeled properly Yes No Describe any Variations Sensitivity Obscuration ft Detector Address Detector Address FAAST System Validation Form CONT GLOSSARY KEY TERMS Configure To set up a program or computer system for a particular application FAAST Fire Alarm Aspirating Sensing Technology High sensitivity aspirating smoke detection system IP Address An Inter...

Страница 12: ...ation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and ser vice during the three year period commencing with the date of manufacture After phon ing System Sensor s toll free number 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid...

Отзывы: