background image

SS-400-012  7 I56-3749-006

Alarm Level

Indicator

Particulate Level

Indicator

Power

Indicator

FIGURE 9. PASSCODE ACCESS BUTTONS

ASP11-00

FIGURE 11. IP ADDRESS BLINK MODE

FIGURE 12. IP ADDRESS INDICATOR LIGHTS

ASP15-00

ASP19-00

DAY, NIGHT AND WEEKEND MODE

If Acclimate mode is not desired, the FAAST system can operate in a simple 
day, night and weekend mode. This allows the device to have separate thresh-
old levels for each state. Times can be configured, if desired, for entering and 
leaving day and night time operation. The device has an internal time refer-
ence (clock) and automatically switches to the weekend mode for Saturday 
and Sunday.

ISOLATION

Isolation mode is initiated by pressing and releasing the ISOLATE button on 
the user interface when the button is enabled (refer to the passcode section). 
When the ISOLATE button is activated the FAAST system resets the fault and 
alarm relays.  It then sets the isolation relay and the isolation fault indicator 
illuminates on the user interface. In this mode the device operates normally 
but will not activate relays for any alarm or fault levels (except the Isolation 
relay).  Fire and fault events can still be seen on the user interface and the web 
server will send e-mail notification of events if enabled. Isolation mode will 
be held through resets and power outages. The device will remain in isolation 
mode until the isolation mode is removed by pressing the ISOLATE button. 
ISOLATE mode may be enabled and disabled using the monitoring portion 
of PipeIQ.

DISABLE

Disable mode is initiated by pressing and holding the ISOLATE button on the 
user interface for 3 seconds when the button is enabled (refer to the passcode 
section). When the ISOLATE button is activated, the FAAST system resets the 
fault and alarm relays.  It then sets the isolation relay and the isolation fault 
indicator illuminates on the user interface. In this mode the fan switches off 
and the device does not report any alarm or fault levels on the user interface 
or activate any relays (except the Isolation Relay). This mode should only 
be used when the system needs to be taken offline. This mode will be held 
through resets and power outages. The device will remain in disable mode 
until the disable mode is removed by pressing the ISOLATE button. Disable 
mode cannot be enabled or disabled using the monitoring portion of PipeIQ.

USER BUTTON ALTERNATE FUNCTIONS

Passcode Access

The user interface has an option that requires users to enter a security code 
before the front panel functions become active. All passcodes must be 4 digits 
in length using numbers 1 through 9 (zero cannot be used). Passcodes may 
only be changed through the PipeIQ software program. In addition, the con-
figuration software tool is capable of locking out buttons individually, so that 
certain buttons may be accessed without a passcode, if desired.

The default passcode is ‘1111’.

The TEST button enters digits, the RESET button is used to enter the unlock 
mode and the ISOLATE button increments the current digit.

To enter the passcode mode, press and hold the RESET button for 8 seconds. 
The first segment on the flow indicator first illuminates yellow, then green. 
When the segment illuminates green, release the RESET button. The first seg-
ment on the airflow display blinks green, indicating the device is ready to 
accept the first digit.

To enter the passcode, use the ISOLATE and TEST buttons, shown in Figure 9. 
The ISOLATE button is used to increment the current digit. As the current digit 
is incremented the segments of the Particulate Bar Graph illuminate accord-
ingly. To complete entry of the digit, press the TEST button. As each digit is 
entered the airflow segment illuminates solid green and the next segment be-
gins to flash, indicating the next digit is ready to be entered. After the 4th digit 
is entered, the fault indicator illuminates green, if the passcode was accepted 
and remains green as long as the detector is “unlocked”. If the passcode was 
not accepted, the fault indicator illuminates amber for 3 seconds then the 
device returns to its previous state.

Once the passcode is accepted, the locked out button(s) become active. After 45 
seconds of inactivity the fault indicator begins to blink green. After an additional 
15 seconds the detector re-locks the button(s) and returns to normal operation.

Note:  If the RESET button is chosen as a locked button, and a reset is initiated, 

the device requires the passcode to regain access to the RESET button.

Address Blink Mode

The unit has two types of addressing capabilities. In addition to the IP Ad-
dress, the FAAST system can also have a local address that is assigned through 
the configuration software. The address can be between 1 and 255. This ad-
dress can be accessed from the user interface by pressing and holding the 
RESET button for 3 seconds. After 3 seconds, the first segment on the airflow 
display illuminates amber, shown in Figure 10, indicating the device is in ad-
dress blink mode. Release the RESET button and the device shows the 3 digit 
number assigned by lighting the particulate bar graph with the appropriate 
number of segments for each digit. The current digit displayed is indicated 
by the 3 left most indicators on the air flow graph. The first digit is the 100’s 
and illuminates for 2 seconds. Next, the tens digit illuminates for 2 seconds, 
followed by the ones digit illuminating for 2 seconds. If one of the numbers is 
zero, then no lights will illuminate for that number on the particulate graph. 
The device then returns to normal operating mode.

IP Address Blink Mode

If the device IP has been lost or is unavailable, it’s possible to obtain the address 
using the IP address blink mode. The IP address can be accessed from the user 
interface by pressing and holding the RESET button for 30 seconds. The digits are 
displayed using the same method described in the address blink mode, except 
that the FAULT and LOW VOLTAGE indicators are used to show the 1st and 12th 
digit, respectively. The device gives the 12 digit number by illuminating the par-
ticulate bar graph to the appropriate number of segments for each digit, as shown 
in Figure 11. The example shown in Figure 11 shows that the 5th number of the 
IP address is 7. The current digit displayed is indicated by the FAULT, FLOW /
FAULT and VOLTAGE indicators (figure 12) starting with the FAULT for the 1st 
digit, progressing through the HIGH FLOW, and ending with the LOW VOLTAGE 
for the 12th digit. If one of the numbers is zero, then no lights will illuminate for that 
number on the particulate graph. The device will return to normal operating mode.

FIGURE 10. ADDRESS BLINK MODE

ASP12-00

Содержание 8100A FAAST

Страница 1: ...s 5 26 kg includes packing material 8100A FAAST Fire Alarm Aspiration Sensing Technology 6581 Kitimat Rd Unit 6 Mississauga Ontario L5N 3T5 1 800 SENSOR2 Fax 905 812 0771 www systemsensor ca INSTALLATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS INTRODUCTION SCOPE OF THIS MANUAL 2 DESCRIPTION FEATURES 2 ITEMS INCLUDED WITH UNIT 2 INSTALLATION PIPE INSTALLATION 2 PHYSICAL UNIT INSTALLATION 2 S...

Страница 2: ...fe Electronic filter life monitoring Ultrasonic air flow sensing Field service access door Easy access filter maintenance door Event service and trend logs Pipe modeling software Acclimate mode operation for auto adjustment of sensitivity Remote monitoring via Ethernet IP Remote reset dry contact input Multi lingual support E mail notification of alarm fault or isolate conditions ITEMS INCLUDED WI...

Страница 3: ...me circumstances when it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit The output ports are tapered the same as the input ports to provide fast easy push fit connection of an exhaust pipe to the unit Perform the following pro cedure to connect the exhaust pipe to the unit 1 Square off and de burr the end of the exhaust pipe Ensure t...

Страница 4: ...ns to flow out of the exhaust port 6 Connect a computer with the PipeIQ software installed to the unit using the Ethernet connection on the bottom of the unit 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 When the configuration is complete remove the Ethernet connection to the unit USER INTERFACE The user interface shown in Figure 4 provides t...

Страница 5: ...l operation two adjacent indicators are green and correspond to the current air flow entering the detector When airflow is at a balanced level the two green segments are centered on the graph at levels 5 and 6 see Figure 7 As air flow rises and falls the green segments move right and left accordingly The segment on the far left represents a decrease in airflow of 20 Conversely movement to the segm...

Страница 6: ...he user interface when the button is enabled refer to pass code access section for activation details Test mode simulates a fire con dition activating all ten segments in the Particulate Level display and each segment in the Alarm display Each corresponding alarm relay is also acti vated after any programmed delay associated with that relay Activation of the RESET button removes the device from TE...

Страница 7: ...ESET button The first seg ment on the airflow display blinks green indicating the device is ready to accept the first digit To enter the passcode use the ISOLATE and TEST buttons shown in Figure 9 The ISOLATE button is used to increment the current digit As the current digit is incremented the segments of the Particulate Bar Graph illuminate accord ingly To complete entry of the digit press the TE...

Страница 8: ...etector events Up to 18 000 events can be stored Events that are tracked include alarms faults and user actions Event tracking data may be accessed via the network through the PipeIQ software or the Web server in terface Configuration and management of the log are done using the PipeIQ software Data Trend Log The FAAST system tracks trend data for each 24 hour time period up to 1 year The device r...

Страница 9: ...UL Tested and approved aerosol smoke products are listed in Table 6 MAINTENANCE The only periodic maintenance required is to replace the filter assembly when the filter light is illuminated Perform the following procedure to replace the filter assembly 1 Remove power from the system 2 Open the door on the right side of the device that covers the LED system indicators 3 Remove the plastic name card...

Страница 10: ...ess Contact information Date Wiring Checked Date Yes No Detector Settings Checked Date Yes No Test Relays Date Yes No REQUIRED DOCUMENTS Copy of Commissioning Form Yes No FAAST system Bill of Material Yes No Commissioning Form for each system Yes No Smoke Test results optional Yes No Locally required forms Yes No Customer s Signature Date Commissioning Agent Signature Date FAAST System Validation ...

Страница 11: ...y Yes No Is the pipe network installed and labeled properly Yes No Describe any Variations Sensitivity Obscuration ft Detector Address Detector Address FAAST System Validation Form CONT GLOSSARY KEY TERMS Configure To set up a program or computer system for a particular application FAAST Fire Alarm Aspirating Sensing Technology High sensitivity aspirating smoke detection system IP Address An Inter...

Страница 12: ...ation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and ser vice during the three year period commencing with the date of manufacture After phon ing System Sensor s toll free number 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid...

Отзывы: