background image

SS-400-012  6 I56-3749-006

MODES OF OPERATION

INITIALIZATION

When the FAAST system is first installed it is not configured and gives a fault 
indication by illuminating the configuration fault LED indicator. This indicates 
that the device has not had its initial configuration loaded and remains in this 
state until it is initially configured (refer to the Configuration section below for 
further instructions). Once configuration has started, the device performs an 
automatic initialization. This initialization sets the air flow baseline, the filter 
clogged baseline and the particulate level baseline. It is important that the sys-
tem is connected properly and the filter is installed correctly when the device 
is initialized. These initial readings are used as a reference baseline to indicate 
when a fault occurs. Innitialization may take up to five minutes to complete.

STARTUP

Once powered, the FAAST system scrolls the particulate display in green for 
one second and then initializes using its stored configuration. The device 
checks and establishes its initial airflow, filter and fan settings. If all measure-
ments are normal it begins normal operation. If any fault is detected the ap-
propriate fault LED will illuminate.

CONFIGURATION

The FAAST system is configured using the software included in PipelQ. Data 
is sent via the built-in Ethernet connection. The device receives the configura-
tion and performs a validation before the configuration becomes active. After 
validation of the data, the device performs an initialization with the new con-
figuration.

Failure of Configuration Validation

If configuration validation fails, the software configuration tool indicates a 
failure and the FAAST system illuminates the amber CONFIGURATION fault 
LED on the user interface. The device will not accept any of the data as valid. 
If a configuration fault occurs during the initial configuration or the device is 
unable to operate due to the configuration, a Major fault relay will be set.  The 
device must be re-configured using PipeIQ.  If the configuration fault occurs 
after the initial configuration has been accepted, a Minor Fault relay will be set 
and the device reverts back to its last valid configuration.

Power or Network Loss during Configuration

During an upload of configuration data, the FAAST system keeps the last 
known valid configuration in memory until a complete validation is com-
pleted on the new configuration data. This prevents data corruption in the 
event of a power loss or network failure. When power is restored the device 
performs a Startup with the last valid configuration. The device also indicates 
a CONFIGURATION fault on the user interface and sets the Minor Fault Relay. 
This occurs only once. When the next Reset or Power On Reset is performed 
the device continues to use the last valid configuration.

NORMAL MODE

In Normal operating mode the FAAST system displays the air flow and current 
particulate levels on the user interface. The particulate level is compared to 
the threshold levels programmed into the device and activates the appropriate 
alarm as particulate levels exceed that threshold. If any fault occurs it acti-
vates the corresponding fault LED and relay.

TEST MODE

Test mode is initiated through the PipeIQ Live View tab or by depressing the 
TEST button on the user interface, when the button is enabled (refer to pass-
code access section for activation details). Test mode simulates a fire con-
dition, activating all ten segments in the Particulate Level display and each 
segment in the Alarm display. Each corresponding alarm relay is also acti-
vated after any programmed delay associated with that relay. Activation of the 
RESET button removes the device from TEST mode.

RESET MODE

Reset mode is initiated through the PipeIQ Live View tab or by depressing the 
RESET button on the user interface, when the button is enabled (refer to pass-
code access section for activation details). When RESET is activated all relays 
are reset. The device then enters Normal mode operation. If any fault or alarm 
states remain, the device re-activates the state automatically.

ACCLIMATE™

The FAAST system includes an available Acclimate mode. By allowing the de-
vice to operate in Acclimate mode, a device’s susceptibility to nuisance alarms 
can be reduced. This provides maximum protection for a device located in 
changing environments. The sensitivity of the unit continuously adjusts over 
time, within the set limits as the local environment changes. Acclimate mode 
must be activated and configured with the software configuration tool which 
is part of the PipeIQ software package. In Acclimate mode the device automat-
ically adjusts the alarm point between a specified minimum and maximum 
sensitivity, programmed by the user. For the first 24 hours of operation the 
device monitors its environment. After the initial 24 hour period, the device 
adjusts the alarm point based on the particulate levels over a rolling 1 hour 
period. It then adjusts the alarm level starting from the insensitive boundary, 
based on the stability of the environment being monitored. 

Setting Acclimate mode

The user chooses the boundaries for each alarm level in the Acclimate mode.  
The FAAST system  starts from the insensitive boundary and adjusts itself to 
stay within the sensitive boundary. It is also possible to have a static alarm 
level by adjusting the high and low boundary to the same level. This allows 
the flexibility to maintain acclimating levels for some alarms and static levels 
for others. Table 4 shows the various levels that are available.

Each Acclimate level is also available for monitoring with the PipeIQ tool. 
This allows the user to read the current Acclimated alarm level for each alarm.

ALARM LEVEL

THRESHOLD HIGH  

SENSITIVITY

THRESHOLD LOW  

SENSITIVITY

CURRENT LEVEL

Alert

Alert High

Alert Low

Acclimate Alert Level

Action 1

Action 1 High

Action 1 Low

Acclimate Action 1 Level

Action 2

Action 2 High

Action 2 Low

Acclimate Action 2 Level

Fire 1

Fire 1 High

Fire 1 Low

Acclimate Fire 1 Level

Fire 2

Fire 2 High

Fire 2 Low

Acclimate Fire 2 Level

TABLE 4. ACCLIMATE LEVELS

ALARM LEVEL

DEFAULT THRESHOLD  

%OBS/FT.

PROGRAMMABLE RANGE 

%OBS/FT.

DEFAULT THRESHOLD 

%OBS/M

PROGRAMMABLE 

RANGE %OBS/M

Alert

0.012

0.00046-6.25

0.0396

0.0015-20.5

Action 1

0.050

0.0010-6.25

0.165

0.0033-20.5

Action 2

0.100

0.0030-6.25

0.33

0.0102-20.5

Fire 1

0.250

0.012-6.25

0.825

.039-20.5

Fire 2

0.500

0.012-6.25

1.65

.039-20.5

TABLE 3. ALARM LEVEL PROGRAMMABLE RANGES

NOTE: Installation must be accomplished in accordance with all local codes and regulations. 
Product is ULC certified to CAN/ULC S529. The 8100A FAAST is ULC approved from 0.00046 %/ft obs. to 3.15%/ft obs.  Evacuation via FACP (fire alarm control 
panel) must not be set higher than 0.735 %/ft obs.  Product is approved for air velocity range from 100 to 4000 FPM.

Содержание 8100A FAAST

Страница 1: ...s 5 26 kg includes packing material 8100A FAAST Fire Alarm Aspiration Sensing Technology 6581 Kitimat Rd Unit 6 Mississauga Ontario L5N 3T5 1 800 SENSOR2 Fax 905 812 0771 www systemsensor ca INSTALLATION AND MAINTENANCE INSTRUCTIONS TABLE OF CONTENTS INTRODUCTION SCOPE OF THIS MANUAL 2 DESCRIPTION FEATURES 2 ITEMS INCLUDED WITH UNIT 2 INSTALLATION PIPE INSTALLATION 2 PHYSICAL UNIT INSTALLATION 2 S...

Страница 2: ...fe Electronic filter life monitoring Ultrasonic air flow sensing Field service access door Easy access filter maintenance door Event service and trend logs Pipe modeling software Acclimate mode operation for auto adjustment of sensitivity Remote monitoring via Ethernet IP Remote reset dry contact input Multi lingual support E mail notification of alarm fault or isolate conditions ITEMS INCLUDED WI...

Страница 3: ...me circumstances when it may be necessary to connect a pipe to the exhaust port to divert the exhaust away from the location of the unit The output ports are tapered the same as the input ports to provide fast easy push fit connection of an exhaust pipe to the unit Perform the following pro cedure to connect the exhaust pipe to the unit 1 Square off and de burr the end of the exhaust pipe Ensure t...

Страница 4: ...ns to flow out of the exhaust port 6 Connect a computer with the PipeIQ software installed to the unit using the Ethernet connection on the bottom of the unit 7 Use the PipeIQ software to set up the unit configuration required for the particular application 8 When the configuration is complete remove the Ethernet connection to the unit USER INTERFACE The user interface shown in Figure 4 provides t...

Страница 5: ...l operation two adjacent indicators are green and correspond to the current air flow entering the detector When airflow is at a balanced level the two green segments are centered on the graph at levels 5 and 6 see Figure 7 As air flow rises and falls the green segments move right and left accordingly The segment on the far left represents a decrease in airflow of 20 Conversely movement to the segm...

Страница 6: ...he user interface when the button is enabled refer to pass code access section for activation details Test mode simulates a fire con dition activating all ten segments in the Particulate Level display and each segment in the Alarm display Each corresponding alarm relay is also acti vated after any programmed delay associated with that relay Activation of the RESET button removes the device from TE...

Страница 7: ...ESET button The first seg ment on the airflow display blinks green indicating the device is ready to accept the first digit To enter the passcode use the ISOLATE and TEST buttons shown in Figure 9 The ISOLATE button is used to increment the current digit As the current digit is incremented the segments of the Particulate Bar Graph illuminate accord ingly To complete entry of the digit press the TE...

Страница 8: ...etector events Up to 18 000 events can be stored Events that are tracked include alarms faults and user actions Event tracking data may be accessed via the network through the PipeIQ software or the Web server in terface Configuration and management of the log are done using the PipeIQ software Data Trend Log The FAAST system tracks trend data for each 24 hour time period up to 1 year The device r...

Страница 9: ...UL Tested and approved aerosol smoke products are listed in Table 6 MAINTENANCE The only periodic maintenance required is to replace the filter assembly when the filter light is illuminated Perform the following procedure to replace the filter assembly 1 Remove power from the system 2 Open the door on the right side of the device that covers the LED system indicators 3 Remove the plastic name card...

Страница 10: ...ess Contact information Date Wiring Checked Date Yes No Detector Settings Checked Date Yes No Test Relays Date Yes No REQUIRED DOCUMENTS Copy of Commissioning Form Yes No FAAST system Bill of Material Yes No Commissioning Form for each system Yes No Smoke Test results optional Yes No Locally required forms Yes No Customer s Signature Date Commissioning Agent Signature Date FAAST System Validation ...

Страница 11: ...y Yes No Is the pipe network installed and labeled properly Yes No Describe any Variations Sensitivity Obscuration ft Detector Address Detector Address FAAST System Validation Form CONT GLOSSARY KEY TERMS Configure To set up a program or computer system for a particular application FAAST Fire Alarm Aspirating Sensing Technology High sensitivity aspirating smoke detection system IP Address An Inter...

Страница 12: ...ation of this Warranty shall be limited to the repair or replacement of any part of the smoke detector which is found to be defective in materials or workmanship under normal use and ser vice during the three year period commencing with the date of manufacture After phon ing System Sensor s toll free number 800 SENSOR2 736 7672 for a Return Authorization number send defective units postage prepaid...

Отзывы: