Error
Handling
©
SYS TEC electronic GmbH 2007 L-1032e_9
55
•
CAN- ACK error
Possible causes:
no other CAN device connected to the CAN bus
incorrect CAN bus cabling,
hardware error,
terminating resistors are missing or wrong value
(120 Ohm at both ends are required)
Gateway:
CAN error LED blinks with a 25:75 on/off ratio
until the transmission or receipt of a CAN message
was successful
Ethernet Error
LED
CAN Error
LED
Error Description
illuminates
No connection established via BTP interface
or connection interrupted
illuminates
BTP send buffer overflow (message loss)
illuminates
BTP receive buffer overflow (message loss)
illuminates
Error while sending or receiving over BTP
(message loss)
short flashes
Receive buffer overflow (message loss)
blinks
with
50:50 on/off
ratio
CAN bus-off error detected
blinks
with
25:75 on/off
ratio
CAN acknowledgement error detected
short flashes
Send buffer overflow
Table 7:
Error Display Overview
Содержание GW-003
Страница 1: ...system house for distributed automation CAN Ethernet Gateway GW 003 Systems Manual Edition April 2007 ...
Страница 5: ...Contents SYS TEC electronic GmbH 2007 L 1032e_9 Index 97 ...
Страница 8: ...CAN Ethernet Gateway SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 14: ...CAN Ethernet Gateway 6 SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 56: ...CAN Ethernet Gateway 48 SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 66: ...CAN Ethernet Gateway 58 SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 100: ...CAN Ethernet Gateway 92 SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 108: ...Published by SYS TEC electronic GmbH 2007 Ordering No L 1032e_9 Printed in Germany ...