Device
Functions
©
SYS TEC electronic GmbH 2007 L-1032e_9
31
4.2.4
CAN Interface
A CAN interface is generated by
mkif can 0
with the interface number 0. The directory name is selected
automatically and is
/if/can0
for the first interface. Only one CAN
interface can be active.
Possible Options:
<option> ::={<switch>|<bauidx>|<canid>|<busid>|<bufid>}
<switch> ::= {on | off}
on
initializes the CAN driver
off
switches off the CAN driver (default)
<baudidx> ::= baud:<num>
sets the transfer rate corresponding to the baudrate index
according to CiA DSP305
3
0
= 1 MBit/s (default)
1
= 800 kBit/s
2
= 500 kBit/s
3
= 250 kBit/s
4
= 125 kBit/s
5
= 100 kBit/s
6
= 50 kBit/s
7
= 20 kBit/s
8
= 10 kBit/s
<canid> ::=canid:<hex>
Sets the CAN identifier
<hex>
, which is used when error
messages are sent (default: 0xfe).
Value range: 0<=
hex
<= 7FF
3
CiA DSP305:
CAN in Automation Draft Standard Proposal CANopen Layer Setting
Services and Protocol
Содержание GW-003
Страница 1: ...system house for distributed automation CAN Ethernet Gateway GW 003 Systems Manual Edition April 2007 ...
Страница 5: ...Contents SYS TEC electronic GmbH 2007 L 1032e_9 Index 97 ...
Страница 8: ...CAN Ethernet Gateway SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 14: ...CAN Ethernet Gateway 6 SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 56: ...CAN Ethernet Gateway 48 SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 66: ...CAN Ethernet Gateway 58 SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 100: ...CAN Ethernet Gateway 92 SYS TEC electronic GmbH 2007 L 1032e_9 ...
Страница 108: ...Published by SYS TEC electronic GmbH 2007 Ordering No L 1032e_9 Printed in Germany ...