Edit Communication (cont’d)
The parameters which can be entered in the <spec_block> are
listed below. For any specific <aid> entered in a command, only
certain parameters are valid. For each valid parameter, choose the
appropriate value from the Value column. When entering multiple
parameters, separate the parameters with commas
.
Aid
Parameter
Value
Description
COM-a MONMSG=b
b = ALW
View messages from all ports
b = INH
View messages from this port only
KEEPALIVE=b
b = 1 to
255
Inactive minutes until the unit sends a COMPLD
message to keep the connection from being
closed
b = 0
No COMPLD message is output
ENDOFTEXT=b
b = 1 to 9F
Hex code at end of all responses
b = 0
No hex code at end of responses
ECHO=b
b = ALW
Echoes characters received so they appear on
the user’s screen as typed
b = INH
Local echo is disabled
COMPRI=b
b = ALW0
TL1 commands and responses, no
autonomous messages sent
b = ALW1
TL1 commands and responses, autonomous
messages
b = ALW2
TL1 commands and responses, autonomous
messages whether logged on or not
b = INH
Closes connection, logs off any user (if
logged on), and keeps port from use.
Releases a telnet session from an Ethernet
port (a port cannot close itself)
Содержание TimeSource 500
Страница 1: ...TimeSource 3500 GPS Primary Reference Source 097 72050 01 Issue 7 August 2003 ...
Страница 6: ...6 TimeSource 3500 Contents 097 72050 01 Issue 7 August 2003 ...
Страница 85: ...3 Chapter Installation This chapter is the sequential order of procedures for installation and power up ...
Страница 161: ...4 Chapter TL1 Reference This chapter provides information for using the TL1 language ...
Страница 271: ...6 Chapter Specifications This chapter provides equipment specifications ...
Страница 297: ...Index ...