88
TimeSource 3100
Installation
097-72020-01 Issue 9: November 2003
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
S
3
27
If not using an Element Manager, skip to Step 29. If not using a separate port to send
autonomous messages to an Element Manager, skip to Step 28. Use the Edit Equipment
command to set the IP address and port address of the Element Manager. Port 5550
connects to this address when the TimeSource 3100 develops a TL1 autonomous
message, sends any messages, and closes the connection. An alternate Element Manager
may be set up in case port 5550 cannot make a connection to the primary Element
Manager.
ED-EQPT::TS3100:<ctag>:::IPEM1=a,IPEM1PORT=b[,IPEM2=a]
[,IPEM2PORT=b][,IPINACT=c];
IPEM1=a=Primary Element Manager's IP address in the form a.a.a.a (each a is an
independent value of 0 to 255)
IPEM1PORT=b=Primary Element Manager's Ethernet port address (b = 0 to 65535)
IPEM2=a=Alternate Element Manager's IP address in the form a.a.a.a (each a is an
independent value of 0 to 255)
IPEM2PORT=b=Alternate Element Manager's Ethernet port address (b = 0 to 65535)
IPINACT=c= Disconnects from the Element Manager if an autonomous message is not
developed during this number of 100-ms units of inactivity (0 to 10,000, where 0
deactivates the timer)
Procedure E. Power-Up (cont’d)
Step
Procedure
Содержание TimeSource 3100
Страница 1: ...TimeSource 3100 GPS Primary Reference Source 097 72020 01 Issue 9 November 2003 ...
Страница 49: ...3 Chapter Installation This chapter provides the steps required for installation and power up ...
Страница 109: ...Chapter 4 TL1 Reference This chapter provides information for using the TL1 language ...
Страница 203: ...Chapter 6 Specifications This chapter provides equipment specifications ...