Lightning Suppressor Guidelines
•
Mount the lightning suppressor within 4.6 meters of a valid, direct, low impedance,
low resistance, earth ground connection point. Valid earth grounds include the roof
ring ground system, building structural steel, or a Central Office ground plate. If the
grounding point is inside the building, mount the suppressor within 15 meters of the
cable entry into the building.
Warning:
Metal clamps that form a complete metal circle around the antenna cable or
the cable conduit are not allowed. The ring clamp acts like a choke coil to induce
currents, which resists current flow and hampers proper lightning protection.
Warning:
Place the lightning suppressor away from electrical devices or cabling that
may induce arcing.
Note:
Keep all impedances as low as possible, otherwise the grounding scheme may be
defeated.
•
Route the ground wire as straight as possible (bends in the ground wire increase
impedance at lightning frequencies), in accordance with local company practices.
•
Treat all exposed connections with an electrically conductive anti-corrosion
compound (Kopr-Shield or equivalent).
Warning:
Avoid small-radius turns and unnecessary turns.
Содержание TimeSource 3100
Страница 1: ...TimeSource 3100 GPS Primary Reference Source 097 72020 01 Issue 9 November 2003 ...
Страница 49: ...3 Chapter Installation This chapter provides the steps required for installation and power up ...
Страница 109: ...Chapter 4 TL1 Reference This chapter provides information for using the TL1 language ...
Страница 203: ...Chapter 6 Specifications This chapter provides equipment specifications ...