If not using performance monitoring, skip to Step 25. Use the Initialize Register command
to reset the performance monitoring data to zero for all input spans.
INIT-REG-EQPT::SPAN-a:<ctag>::ALL;
a = SPAN input (a = A, B, or ALL)
ALL = resets all performance monitoring data
25
If not using Ethernet, go to Step 29. Use the Edit Equipment command while connected to
COM1, COM2, or the CRAFT port to set the IP address, subnetwork mask, and gateway
address for the current TimeSource 3100 unit, as required for proper operation in the
managed element network. (These parameters affect all Ethernet ports. The Ethernet port
should be closed and all users logged off before issuing this command.)
ED-EQPT::TS3100:<ctag>:::IPNE=a,IPSUBNET=a,IPGATE=a;
IPNE=aThis unit's IP address in the form a.a.a.a (each a is an independent value of 0 to
255)
IPSUBNET=aSubnet mask in the form a.a.a.a (each a is an independent value of 0 to 255)
IPGATE=aGateway IP address in the form a.a.a.a (each a is an independent value of 0 to
255)
Procedure E. Power-Up (cont’d)
Step
Procedure
Содержание TimeSource 3100
Страница 1: ...TimeSource 3100 GPS Primary Reference Source 097 72020 01 Issue 9 November 2003 ...
Страница 49: ...3 Chapter Installation This chapter provides the steps required for installation and power up ...
Страница 109: ...Chapter 4 TL1 Reference This chapter provides information for using the TL1 language ...
Страница 203: ...Chapter 6 Specifications This chapter provides equipment specifications ...