Site Requirements
Environmental Requirements
Revision A, March 1998
Technical Reference
53
Environmental
Requirements
lists the environmental requirements for the command
module.
Table 5
Environment Requirements
#
+ $%
,%#
()
Air flow is from front to back
%
Below Sea Level
Above Sea Level
Operating Range
30.5 m (100 ft.)
3,000 m (9,840 ft.)
Storage Range
30.5 m (100 ft.)
3,000 m (9,840 ft.)
Transit Range
30.5 m (100 ft.)
12,000 m (40,000 ft.)
#%
Optimum
1
22º C (72° F)
Operating Range
1
5º C to 45º C (40º F to 113º F)
Storage Range
-10º C to 50º C (14º F to 120º F)
Transit Range
-40º C to 60º C (-40º F to 140º F)
#%
(maximum allowed)
Operating Range
10º C (18º F) per hour
Storage Range
15º C (27º F) per hour
Transit Range
20º C (36º F) per hour
*%#'
(no condensation)
Operating Range
10% to 90%
Storage Range
10% to 90%
Transit Range
5% to 95%
Max. Dew Point
26º C (79º F)
Max. Humidity Gradient 10% per hour
*
0.329 kVA
214.0 W
731.0 Btu/hr
%
Sound Power
6.5 bels
Sound Pressure
65 dBA
1
If you plan to operate the command module at altitudes between 1000 m and 3000 m (3280 ft. and 9850 ft.), you must lower the environmental
temperature 1.7º C (3.3º F) for every 1000 m (3280 ft.) above sea level.
Содержание J21971S-0398
Страница 1: ...MetaStor Command Module Installation Guide J21971S 0398 Revision A ...
Страница 8: ...vi MetaStor Command Module Installation Guide Revision A March 1998 ...
Страница 10: ...viii MetaStor Command Module Installation Guide Revision A March 1998 ...
Страница 84: ...Index 6 MetaStor Command Module Installation Guide Revision A March 1998 ...
Страница 85: ......
Страница 86: ... Symbios Logic Inc Printed in the USA J21971S 0398 Revision A ...