22
5.4 MAX limit
Choose the minimal output value in the range
of 0 ... 22 mA (Standard 20 mA).
With you set the value to 0.0. With the
numbers you input the beginning value and
with the input is accepted and you quit the
menu level.
5.5 Alarm value
Choose the output value for the alarm
(sensor error or an internal alarm);
at the same time the relay 3 drops down.
Range of 0 ... 22 mA (Standard 3 mA)
With you set the value to 0.0. With the
numbers you input the beginning value and with the input is accepted and
you quit the menu level.
5.6 Filter time
Choose the filter time for the
current output
in the range of 0.1 ... 999.9 s (Standard 1 s).
With you set the value to 0.0. With the
numbers you input the beginning value and
with the input is accepted and you quit the
menu level.
5.7 Calibration: 4 mA
Set the minimal current output. Fit to the
external measurement system (at differing
display).
Adapt the current output to 4 mA with the
keys and quickly and with the keys
and slowly. With the input is accepted and you quit the menu level,
with you quit the menu point without any change.
5.8 Calibration: 20 mA
Set the maximal current output. Fit to the
external measurement system (at differing
display).
Adapt the current output to 4 mA with the
keys and quickly and with the keys
and slowly. With the input is accepted and you quit the menu level,
with you quit the menu point without any change.
C
8
Analogue output
7 8 9
MAX limit
4 5 6
20.0
mA
1 2 3
C
0
8
Analogue output
7 8 9
Alarm value
4 5 6
3.0
mA
1 2 3
C
0
8
Analogue output
7 8 9
Filter time
4 5 6
3.0
s
1 2 3
C
0
8
Analogue output
Calibration 4.0 mA
C
<< <
> >>
8
Analogue output
Calibration 20 mA
C
<< <
> >>
8
C
8
C
8
<<
8
C
>>
<
>
<<
8
C
>>
<
>