Operating Instructions
18
2.3 Alarm Dead Time
Threshold value how long the value must be
over or under the limit until the alarm relay
reacts. Range: 0.1 ... 99.9 s
With leave the menu without any change,
with transfer the entry and leave the
menu level.
2.4 Alarm Hysteresis
Threshold value of the alarm
Range: 0.1 ... 99.9 % of the measuring range.
With leave the menu without any change,
with transfer the entry and leave the
menu level.
2.5 Operation Mode
Choice of the contact work or interruption.
NO - Working current
NC - Static current
With and select according to the
display, with leave the menu without any
change, with transfer the entry and leave the menu level.
2.6 Alarm Sensor Error
Reaction by sensor error to the alarm and
current output. On / Off
With and select according to the
display, with leave the menu without any
change, with transfer the entry and leave
the menu level.
3. ANALOG OUTPUT
With and select according to your
significance, with leave the menu without
any change, with transfer the entry and
switch to a deeper menu level.
3.1 Starting Range
Value for the output min
(standard 4 mA) - Range 0 ... 22 mA
With set the value to 0.0 to start enter the
numbers of the measuring range, with
transfer the entry and leave the menu level.
C
8
8
C
Alarm
7 8 9
Hysteresis
4 5 6
1.0
%
1 2 3
C
0
8
Alarm
7 8 9
Delay
4 5 6
1.0
s
1 2 3
C
0
8
Alarm
£
Operation Mode
¤
NO
C
8
Analog Output
7 8 9
Range set low
4 5 6
4.0
mA
1 2 3
C
0
8
C
8
£
¤
Alarm
£
Sensor Fault
¤
on
C
8
C
8
£
¤
C
8
£
¤
C
8
3. Analog Out
£
3.1 set low
4.0
mA
¤
3.2 End
20.0 mA
3.3 Minimum
0.3 mA
C
3.4 Maximum
21.0 mA
8
q