4. Communication
Physically install the GOLD air handling unit, MIRUVENT
power roof ventilator and the MIRU Control equipment.
See separate installation instructions.
4.1. MIRU Control and MIRUVENT power
roof ventilator
Wiring the connections to MIRU Control
Connect the 3-wire cable to terminals 11 (A), 12 (B) and
13 (GND) on the control circuit card inside the MIRU Con-
trol unit. See illustration.
A twisted-pair cable is recommended.
Wiring the connections to the MIRUVENT
MIRUVENT with AC motor and integrated frequency
inverter
Unfasten and bend up the upper section of the frequency
inverter.
Place the upper section in the groove designed to receive
it in the lower section.
Connect the communication cable to terminals A, B and
GND, next to the Bus marking. See illustration.
MIRUVENT with EC motor and control system
Connect the communication cable to the wiring terminals
inside the safety switch enclosure.
Connect conductor A to terminal 4, conductor B to termi-
nal 5 and GND to terminal 6.
The internal electrical connections to the motor control
system have already been wired.
A B GND A B
-
-
-
GND
8 9 10 11 12 13 14 15 16 17 18 19 20 21
STOP
LS
HS
TEMP
INT.BUS(FAN)
TERM.ON OFF
Control circuit card,
MIRU Control
A
}
(GND)
Control circuit card terminals, frequency inverter, MIRUVENT
B
Bus
L1
N
Aux NO
Aux NO
Aux NC
Aux NC
1
N
6
5
7
8
N
2
2
3
PE
5
6
4
A
GND
B
PE
Terminals in the safety switch enclosure, MIRUVENT
White - orange
Others
Orange