7. Base settings, MIRU Control
connected to the GOLD unit
If one or several MIRU Control units are connected to one
GOLD unit, a number of settings must be entered.
One MIRU Control
If one MIRU Control is connected to the GOLD unit, the
factory preset values apply.
Factory preset values:
Modbus ID = 100
Speed = 38400
Parity = None
Stop bits = 1.
The settings can be checked under Service menu (code
1112) – Communication; see menu.
2 - 10 MIRU Control units
Max. 10 units MIRU Control
can be connected to one GOLD unit.
If two to ten MIRU Control units are connected to one
GOLD unit, the Modbus ID for each MIRU Control must be
unique.
The MIRU Control corresponding to Fan 1 in the GOLD
unit’s hand-held micro terminal, should have Modbus ID
= 100. Fan 2 should have Modbus ID =101. Fan 3 should
have Modbus ID = 102, etc.
In the GOLD unit’s hand-held micro terminal (under instal-
lation – Functions – MIRU Control – Functions OFF/ON),
set Fan 1 = Active. If several MIRU Control units are con-
nected, these fans should also be set = Active.
SERVICE MENU
Flow/Pressure
Communication
Backlight
<Exit Select>
Menu in the control panel, MIRU Control