background image

GB.FUNKMIRU.121204

Swegon reserves the right to alter specifications.

www.swegon.com     9

8. Operating mode settings

MIRU Control

Line 2 in the start menu shows the fan’s current operating 
mode, for example: STOP or LOW SPEED.

Line 3 in the start menu indicates, by showing various 
symbols, how the MIRUVENT power roof ventilator is 
controlled, for example via internal time switch or external 
supervisory system.

Line 4 in the start menu shows the current functions of 
the buttons, for example: Auto, Stop or Menu. "Auto" 
means that one press of the button sets the fan to the 
auto mode. "Stop" means that the fan is operating and 
that one press of the button sets the fan to the stop 
mode.

See illustration.

For further information about the control panel, see the 
separate installation instructions for the MIRU Control 
equipment. 

N.B.!

 The stop input must be connected between terminal 

14 and 15 in order to be able to start the fan.

Operating times via the Miru Control panel

Set the current date and time under Time/Date in the main 
menu.

Four different time channels can be set under Time chan-
nel. 

If the same in-operation times are to apply every day of 
the week (Mon.–Sun.), you need only program one time 
channel. Various in-operation times during the days of the 
week should be programmed in separate time channels 
(Mon.–Fri., Sat.–Sun. or Mon., Tues., Wed., etc.)

Set the low speed or high speed under Operation.

Set the start time (hh:mm) under Start time.

Set the stop time (hh:mm) under Stop time.

Indicates that the MIRUVENT is controlled by any of the exter-
nal inputs: stop, low speed or high speed.

Indicates that the MIRUVENT is controlled by the internal time 
switch to operate at low speed or high speed.
Indicates that the MIRUVENT is controlled by an external 
supervisory system via an external BUS.

MIRU Control 

 

Mon. 22:20

LOW SPEED

Stop Menu

Line 2

Line 3

Line 4

MAIN MENU

Time/Date

Flow/Pressure

<Exit Select>

Time/Date

Sun. 1.1.2010

0:13

Time channel

<Exit Edit>

Control panel, MIRU Control

Button

Содержание MIRU Control

Страница 1: ...l via Modbus 2 Material Specification Control of MIRUVENT fan via MIRU Control MIRU Control equipment TBMZ 11 MIRUVENT fan with type code MIRU x xx xx 3 0 or MIRU x xx xx 1 x x model and size codes Pr...

Страница 2: ...tions cable not included in supply 3 wire Twisted pair cables are recommended If shield is to be used the shield must be con nected to the AHUs roof fans chassi and not connected to MIRU Control not i...

Страница 3: ...requency inverter Place the upper section in the groove designed to receive it in the lower section Connect the communication cable to terminals A B and GND next to the Bus marking See illustration MI...

Страница 4: ...white tapping to pressure port on the pressure sensor Set the pressure sensor function selector switch to position 0 See illustration Connect the modular cable to an optional modular con nection in th...

Страница 5: ...e DIN rail inside the electrical cubicle of the GOLD unit or on another appropriate loca tion near this cubicle Connect the modular cable between one of the modular connections on the cable adapter an...

Страница 6: ...ld be set to the ON position See illustration If several MIRU Control units are connected to the same GOLD unit the MIRU Control that is last in the communi cation loop should have its jumper JP2 TERM...

Страница 7: ...y setting m s Fan regulation control MIRU Control is factory preset for pressure regulation Press reg sensor ON Pressure regulation requires connection of a pressure sensor set for pressure regulation...

Страница 8: ...see menu 2 10 MIRU Control unitsMax 10 units MIRU Control can be connected to one GOLD unit If two to ten MIRU Control units are connected to one GOLD unit the Modbus ID for each MIRU Control must be...

Страница 9: ...er to be able to start the fan Operating times via the Miru Control panel Set the current date and time under Time Date in the main menu Four different time channels can be set under Time chan nel If...

Страница 10: ...sed by the corresponding rate If EA is selected the extract airflow in the GOLD unit will be decreased by the corresponding rate Under Miru Control Time channel you must select the following for each...

Страница 11: ...ncy inverter 5 flashes Phase failure on supply voltage phase lacking 6 flashes Fluctuating supply voltage between phases 10 flashes Communication failure between upper and lower sections 11 flashes Me...

Страница 12: ...ng is correct the lower LED on the pressure sensor should be lit with a steady flow and the upper LED should be flashing No 4 PRESSURE SENSOR DEFECTIVE MIRU Control cannot establish correct communicat...

Отзывы: