56
Operation and maintenance instructions
- Conditions:
• Only with post heating or cooling option.
- Causes:
• This alarm indicates that the supply temperature (T5) is lower than 5°C. The fans are stopped for 1 minute.
The alarm is configurable through the advanced setup and is disabled by default.
- Effects:
- Conditions:
Only with internal hydraulic post heating coil (IBA), or external heating coil (EBA).
- Causes:
Indicates that the anti-frost protection temperature of the hydraulic coil is lower than 4°C (configurable through advanced
setup, it is important to reduce this Setting for BAin coil if an antifreeze is in the fluid). The 3-way valve is automatically
opened at 100% for 15 minutes and the heating demand contact is closed (output DO7, see point 4.1, figure 1). If the AHU is
running, the alarm is sent after 2 minutes for a preheating coil and immediately for the others; if the AHU is not running, the
alarm is sent after 5 minutes.
- Effects:
8.17 TYPE 16: ALARM INDICATING THAT THE SUPPLY T° IS TOO LOW
8.18 TYPE 17: ALARM INDICATING HYDRAULIC COILS FROST PROTECTION ALERT
TAC control board
ALARM OUTPUT
AL dPa OUTPUT
LED ALARM
Fans
Alarm Status
/
ON
Stopped
Manual reset mandatory.
TAC control board
ALARM OUTPUT
AL dPa OUTPUT
LED ALARM
Fans
Alarm Status
/
ON
Stopped
Manual reset mandatory.
Displayed on HMI TACtouch
Code
Text displayed
Level
A.40
Anti-freeze protection of the internal post-heater (IBA)
3
A.41
Anti-freeze protection of the waterborne post-heater (EBA+)
3
A.42
Anti-freeze protection of the waterborne post-cooler (EBA-)
3
A.43
Anti-freeze protection of the waterborne reversible coil (EBA+-)
3
Displayed on HMI TACtouch
Code
Text displayed
Level
S.50
Post-heating - T° of the supply air too low
0
S.65
Supply air T° too low - Fan stopped
3