47
Operation and maintenance instructions
- Conditions:
• Fire alarm input must be connected to a fire detection system.
- Causes:
•
Activation of fire alarm input, IN1, connected to a fire detection system.
IN1 can be configured to work as NO open contact by default or as NC if configured so in the advanced setup.
- Effects:
*
The fans run by default in the event of a fire alarm at the configured fixed airflows in the advanced setup. The fans may be
forced to stop in case of fire alarm thanks to contact IN7 and IN8 for supply and exhaust respectivelly (need to be closed).
These contacts are available on optional satellite board SAT IO (see point 4.1).
8.6 TYPE 6: FIRE ALARM
TAC control board
ALARM OUTPUT
AL dPa OUTPUT
LED ALARM
Fans
Alarm status
/
ON
*
Auto reset: no
Displayed on HMI TACtouch
Code
Text displayed
Level
F.10
FIRE ALARM
3
F.11
End of the fire alarm
3