33
Operation and maintenance instructions
Temperature
The temperature control can be configured as a supply air control or an extract
air control. By default, this function is configured as a supply air temperature
control. Changes to this configuration are done in the advanced setup; see
Section 6.1.4
Setting
Settings
range
Factory
setting
T° heating
0...45°C
20,0°C
T° Cooling
0...99°C
24,0°C
T° Freecooling
0...99°C
15°C
Fire Alarm
An external fire detection system is used to control the air handling unit in case
of emergency. The fire alarm function is activated by means of digital input
IN1.
Setting
Settings
range
Factory
setting
Input
Normally open
Normally closed
Normally
closed
Supply airflow
0...max
Extract airflow
0...max
Periodic maintenance
Built-in timer for maintenance warning; if the maintenance interval is
exceeded, a maintenance reminder will be displayed.
Setting
Settings
range
Factory
setting
3 monthly warning
Yes
No
No
12 monthly warning
Yes
No
No
Commissioning completed
When the commissioning has been successful and this is confirmed in this
menu, the commissioning menu will not be activated automatically anymore.
Setting
Settings
range
Factory
setting
Confirmation of
successful commis-
sioning
Yes
No
No
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
LANGUAGE
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
UNITS
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
AIRFLOW REGULATION
TEMPERATURE
FIRE ALARM
BASIC SETUP
PERIODIC MAINTENANCE
PERIODIC MAINTENANCE
COMMISSIONING COMPLETED